HomeYour location:Homelow-voltage electrical apparatusLow voltage transformerMiniature transformer → CTY500,CTY600 Miniature anti DC shunt current transformer
Column tabs 
Product name: CTY500,CTY600 Miniature anti DC shunt current transformer
specification: CTY500,CTY600 Miniature anti DC shunt current transformer
  Zoom Zoom in on the image
Category: low-voltage electrical apparatus -- Miniature transformer
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


CTY500,CTY600 Miniature anti DC shunt current transformerDetailed product description:Column tabs
Technical features of CTY500 and CTY600 miniature anti DC shunt current transformers:

Active type, customizable input/output current
Compact and lightweight, easy to solder directly onto printed circuit boards
High electromagnetic isolation, high precision, and no drift
ABS flame retardant shell, fully resin sealed, high pressure resistance, high reliability

Model number

CTY500

CTY600

Physical appearance picture

Outline drawing 1 of CTY500 and CTY600 miniature anti DC shunt current transformers

Outline drawing 2 of CTY500 and CTY600 miniature anti DC shunt current transformers

Application scenarios

Lead output type

Lead output type

Rated input

100A

200A

rated output

20mA

40mA

accuracy class

0.1%

0.1%

Maximum phase shift

10 ’

5 ’

load resistor

5/10/20/100 Ω

5/10/20/100 Ω

power frequency withstand voltage

3000V/50Hz/1min

overload capacity

100A

200A

Normal working environment

Environmental temperature: -25~60℃

Humidity: 5%~95%

Atmospheric pressure: altitude 2000M and below(For applications in high-altitude areas, please specify when placing an order))

Appearance and installation diagram

CTY500, CTY600 miniature anti DC shunt current transformer installation size 1

Installation size 2 for CTY500 and CTY600 miniature anti DC shunt current transformers

CTY500, CTY600 miniature anti DC shunt current transformer installation size 3

CTY500, CTY600 miniature anti DC shunt current transformer installation size 4

Reminder

Primary input current 1~100A(Specify when ordering))Secondary output current of 1-20mA(Specify when ordering))Secondary direct resistance sampling

Primary input current 1-200A(Specify when ordering))Secondary output current 1~40mA(Specify when ordering))Secondary direct resistance sampling


CTY500, CTY600 miniature anti DC shunt current transformer model description

CTY500,CTY600 Miniature anti DC shunt current transformer
Product Category