HomeYour location:Homelow-voltage electrical apparatusrelayintermediate relay → DZS-500T series intermediate relay
Column tabs 
Product name: DZS-500T series intermediate relay
specification: 暂无图片
  Zoom No image available
Category: low-voltage electrical apparatus -- intermediate relay
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


DZS-500T series intermediate relayDetailed product description:Column tabs

The DZS-500T series intermediate relay is applied in protection and automatic control circuits with DC voltage up to 220V, and it has a small delay when the relay is activated or released according to its working requirements.

Overview of the Structure of DZS-500T Series Intermediate Relays
2.1 The DZS-500T series intermediate relay adopts a protruding installation, and the main body is installed in a plug-in structure housing.
The appearance and installation dimensions of DZS-500T are shown in Figure 2.
The main body of the intermediate relay in the DZS-500T series is the same as that of the DZS-500.
The internal wiring diagram of DZS-500T is shown in Figure 1.


DZS-500T series intermediate relay wiring diagram

Figure 1 Internal wiring diagram of DZS-500T series intermediate relay
According to this, DZS-512T, 532T DZS-513T, 533T DZS-514T, 534T DZS-515T, 535T

Installation dimensions of DZS-500T series intermediate relay

Figure 2: Outline and Installation Dimensions of DZS-500T Series Intermediate Relay

3 DZS-500T series intermediate relay technical data
3.1 Relay model and specification parameters.

model

coil voltage

Number of contact points

Time (S)

Dynamic combination

transformation

DZS-512T

twenty-four

forty-eight

one hundred and ten

two hundred and twenty

two

Action time not less than 0.06

DZS-513T

two

two

DZS-514T

four

DZS-515T

six

DZS-533T

twenty-four

forty-eight

one hundred and ten

two hundred and twenty

two

Release time not less than 0.12

DZS-534T

two

two

DZS-535T

four

DZS-535T

six


3.2 The working environment temperature of the relay is -25 ℃ to+40 ℃.
When the temperature of the surrounding medium is+20 ℃, the operating voltage of the relay should not exceed 70% of the rated voltage. At the rated voltage, the coil circuit should be cut off, and the relay should reliably return to its original position.
When the temperature of the surrounding medium is+20 ℃ and the rated voltage is suddenly applied to both ends of the DZS-510T relay coil, the action time of the relay should not be less than 0.06s.
When the temperature of the surrounding medium is+20 ℃ and the DZS-530T relay coil is energized for not less than 0.5s at rated voltage, the coil circuit should be cut off, and the return time of the relay should not be less than 0.12s.
3.6 Disconnect and connect capacity of relay contacts.
3.6.1 In a DC circuit, when the voltage does not exceed 250V, the current does not exceed lA, and there is an inductance (time constant not greater than 5 × 10-3s), the breaking power of the contacts is 50W.
3.6.2 In an AC circuit, when the voltage does not exceed 250V, the current does not exceed 2.5A, and the power factor is not less than 0.8, the breaking power of the contacts is 500VA.
3.6.3 When the contacts of the relay are in the closed position, they should be able to flow 5A current for a long time with a temperature rise not exceeding 65k.
When the temperature of the surrounding medium is+40 ℃, the coil of the relay can withstand 110% of the rated voltage for a long time, and the temperature rise of the coil does not exceed 65k.
The dielectric strength between the coil and all conductive parts of the relay and the iron core should be able to withstand a test voltage of 50Hz and 2kV AC for 1 minute without breakdown or flashover.
3.9 The power consumption of the coil at rated voltage shall not exceed 5W.
The load on the relay contacts of 3.10 shall meet the requirements of 3.3, 3.4, 3.5, and 3.6 even after withstanding 1000 turns on and 1000 turns off tests under the allowable power conditions specified in Article 3.6.
3.11 For 220V voltage coils with a wire diameter greater than 0.09, short-term power supply is considered; for coils with a wire diameter less than 0.09, long-term power supply is considered.

4 Ordering Instructions
4.1 Name, model, and specifications of the relay.
4.2 Rated voltage and current.
DZS-500T series intermediate relay(No image available)
Product Category
All product information on this website is translated by Baidu machine translation, which may not be completely accurate and is only for reference