HomeYour location:Homelow-voltage electrical apparatusrelayintermediate relay → DZS-100 series intermediate relay
Column tabs 
Product name: DZS-100 series intermediate relay
specification: DZS-100 series intermediate relay
  Zoom Zoom in on the image
Category: low-voltage electrical apparatus -- intermediate relay
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


DZS-100 series intermediate relayDetailed product description:Column tabs
Application of DZS-100 series intermediate relay

The DZS-100 series intermediate relay is used as an auxiliary relay in DC operated protection circuits to increase the number or capacity of contacts for the main protection relay. DZS-115 and DZS-117 are delay action relays; DZS-127 and DZS-136 are delayed voltage action and current holding relays; The DZS-145 type is a delayed return relay.

Overview of the Structure of DZS-100 Series Intermediate Relays
The DZS-100 series relay is a pull in electromagnetic relay.
The coil of the relay is mounted on the cylindrical iron core of the mountain shaped magnetic conductor, DZS-115、 The 117 type has only one working winding (voltage winding); DZS-127、 The 136 type has one working winding (voltage winding) and two holding windings (current winding). Damping rings are simultaneously installed on the cylindrical core above or below the coil, thereby obtaining delayed action or delayed return of the relay.
The dynamic and static contact systems of the relay are respectively fixed on the armature and yoke of the magnetic conductor. The armature and yoke are hinged with support pillars, and the relay is returned and in the open position by the action of a tension spring.
The relay is installed on a vertical panel and can be wired in front of or behind the board. Its internal wiring is shown in Figure 1.

DZS-100 series intermediate relay contact diagram

Figure 1 Internal wiring diagram of DZS-100 series relay
According to this, DZS-115 and DZS-117
DZS-127 DZS-136 DZS-145

3 Technical data
3.1 The rated values and contact forms of relays are given in Table 1.

model

rated value

Number of contact points (paid)

Voltage (V)

Current (A)

Dynamic combination

Dynamic interruption

DZS—115 145

220,110,48,24

two

two

DZS—117

220,110,48,24

four

DZS—127

220,110

1,2,4

four

48,24

2,4,6

DZS—136

220,110

1,2,4

three

48,24

2,4,6


3.2 Operating voltage: not exceeding 70% of the rated voltage.
3.3 Action time: not less than 0.06s (excluding DZS-145 type).
3.4 Holding current: not exceeding 80% of rated current (only referring to DZS-127, 136)
3.5 Return time:
DZS-145 type, at rated voltage, the power on time is not less than 0.5s, and then the power is cut off for not less than 0.8s.
3.6 Thermal performance: When the ambient temperature is+40 ℃;
3.6.1 The voltage winding can withstand 110% of the rated voltage for a long time, not exceeding 65K;
3.6.2 The current winding is allowed to pass 3 times the rated current for 5 seconds;
3.7 Power consumption: At rated value:
3.7.1 DZS-115、 Type 117, not exceeding 3.5W;
3.7.2 DZS-127、 136 type, voltage winding not exceeding 5.5W, current winding not exceeding 2.5W;
3.7.3 DZS-145 type, not exceeding 6.5W.
3.8 Contact Capacity: Complies with the specifications in Table 2.

Load

Voltage (V)

Maximum disconnect current

Long term connected current

DC

AC

(A)

(A)

No sensation

two hundred and twenty

one

five

one hundred and ten

five

five

Feeling it

(T≤5×10-3s)

two hundred and twenty

zero point four

five

one hundred and ten

four

five

cosф=0.4

two hundred and twenty

five

five

one hundred and ten

ten

five


3.9 Dielectric strength: Each circuit of the relay can withstand AC 50Hz and voltage of 2kV between exposed non charged metal parts and circuits that are not electrically connected. The test lasts for 1 minute without breakdown or flashover.
3.10 Relay weight: not exceeding 1.1kg.
3.11 The external dimensions and opening dimensions of DZS-100 series relays are shown in Figure 2 and Figure 3.

DZS-100 series intermediate relay appearance and installation dimensions
Figure 2 Outline dimension diagram
DZS-100 series intermediate relay installation hole size
Figure 3 Hole Size Diagram


3.12 The resistance value of the coil is shown in Table 3.

DZS—

one hundred and fifteen

one hundred and seventeen

Voltage working winding

DC voltage

220V

110V

48V

24V

coil resistance

16300Ω

4080Ω

940Ω

208Ω

one hundred and twenty-seven

one hundred and thirty-six

Voltage working winding

DC voltage

220V

110V

48V

24V

coil resistance

10kΩ

2.5kΩ

480Ω

120Ω

one hundred and forty-five

Voltage working winding

DC voltage

220V

110V

48V

24V

coil resistance

10.2kΩ

2.2kΩ

450Ω

95Ω



4 Ordering Instructions
Please indicate when placing an order
4.1 Name and model of relay.
4.2 Rated voltage and rated current.
4.3 Wiring method: Wiring before or after the board (if not specified, provide wiring accessories according to the wiring after the board)
DZS-100 series intermediate relay
Product Category
All product information on this website is translated by Baidu machine translation, which may not be completely accurate and is only for reference