ZJ6 type intermediate relayDetailed product description:Column tabs
Application of ZJ6 type intermediate relay

ZJ6 type intermediate relay (hereinafter referred to as relay) is used in AC operation circuits as an auxiliary relay to expand the control circuit. 2 Working principle and structure
2.1 This relay is an electromagnetic valve type instantaneous action relay, installed on a rubberwood base and covered with a plastic shell. The electromagnet of the relay is fixed on the bracket of the contact system, and the mechanical connection between the armature and the contact system relies on the bent plate on the fixed armature and the top plate located at the end of the bent plate. When the armature is engaged, the top plate pushes the contact piece, causing the dynamic contact point to close and the dynamic contact point to disconnect.
2.2 The primary winding of the saturated AC converter in the relay is connected to the secondary circuit of the instrument transformer. The primary winding of the saturated inverter has two windings, which can be connected in series or parallel.
2.3 The coil of the relay passes through a bridge rectifier composed of diodes and is connected to the secondary circuit of a saturated inverter. A capacitor is connected to the saturated inverter circuit to reduce the peak voltage.
2.4 The relay is controlled by the dynamic breaking contacts of other relays, and the dynamic breaking contacts are connected to 7 and 9. If action signal display is required, a DX-11/0.05A signal relay can be connected to terminals 11 and 13, or two DX-11/0.025A signal relays can be connected in parallel. If not needed, short-circuit with a connecting piece.
The 2.5 relay has one set of conversion contacts and one set of high-capacity main conversion contacts.
2.6 In order to eliminate the misoperation of the controlled switch caused by the unreliable closure of the dynamic breaking contact during conversion, the large capacity main contact can be wired as shown in Figure 1.
2.7 The relay is fixed on a vertical panel and can be wired in front or behind.
2.8 The internal wiring of the relay is shown in Figure 2. The outline drawing and installation dimensions are shown in Figure 3.

ZJ6 type intermediate relay wiring diagram
Figure 1 Large Capacity Main Contact Connection Method Figure 2 Internal wiring diagram

ZJ6 type intermediate relay installation size 1
Front wiring
ZJ6 type intermediate relay installation size 2
Rear wiring
Figure 3 Outline drawing and installation dimension drawing

Technical data of ZJ6 intermediate relay
3.1 Relay operating value: When the primary two windings of the saturated inverter are connected in series, the operating value is 2.5A, and when the two windings are connected in parallel, the operating value is 5A.
3.2 The large capacity main contact of the relay can withstand an overload of 150A for 4 seconds with a long-term current of 10A.
3.3 The action time at twice the action value shall not exceed 0.05s.
3.4 The power consumption at twice the action value shall not exceed 6VA.
The 3.5 large capacity main contact can shunt and disconnect the trip coil when the current reaches 150A.
3.6 The general contacts of the relay can disconnect AC circuits with a voltage not exceeding 250V, a current not exceeding 2.5A, and a capacity of 450VA (power factor of 0.4 ± 0.1), connect AC circuits with a current not exceeding 15A, a voltage not exceeding 220V, and a capacity of 1000VA.
3.7 The relay should be able to withstand a dielectric strength test of AC voltage of 2kV, 50HZ for 1 minute.
The weight of the 3.8 relay shall not exceed 1.3kg.

4 Ordering Instructions
Please specify when placing an order
4.1 Name and model of relay;
4.2 Wiring method, in order to supply a complete set of components for front or rear wiring;
4.3 Order quantity;
4.4 Ordering method.