LDJ-10Q/210, LDJ2-10Q/210-Y current transformers are epoxy resin cast insulation, fully enclosed, indoor products, suitable for use in circuits with a frequency of 50Hz, rated voltage of 10KV and below, for current and energy measurement and relay protection (especially suitable for KYN handcart switchgear).
The product performance meets the standards GB1208 and IEC60044-1
Rated insulation level 12/42/75KV
Power factor of load: cos φ=0.8 (lag)
Rated frequency 50Hz or 60Hz
Rated primary current: 5-3150A
Rated secondary current: 5A or 1A
Environmental temperature: -5 ℃ to+40 ℃
Measurement accuracy levels: 0.2S, 0.5S, 0.2, 0.5
Technical parameters of LDJ1-10Q/210-Y current transformer
Rated current ratio (A)hierarchical combinationRated output (VA)One second thermal stability current (KA)Dynamic stability current (KA)
| 0.2s | 0.5s | 0.2s | 0.5s | 10P10 |
| 5/5 | 0.2s/10P 0.2/10P 0.5/10P | ten | ten | ten | ten | fifteen | zero point five | one point two five |
| 10/5 | one | two point five |
| 15/5 | one point five | three point seven five |
| 20/5 | two | five |
| 30/5 | three | seven point five |
| 40/5 | four | ten |
| 50/5 | seven point five | eighteen |
| 75/5 | eleven | twenty-eight |
| 100/5 | fifteen | thirty-seven point five |
| 150/5 | twenty-two point five | fifty-six |
| 200/5 | thirty | seventy-five |
| 300~400/5 | sixty-three | one hundred |
| 500~800/5 | fifteen | fifteen | twenty |
| 1000~1250/5 | twenty | twenty | twenty-five | eighty | one hundred and thirty |
LDJ1-10Q/210-Y type current transformer