Product name: TD-12/1600-31.5 Ceramic vacuum arc extinguishing chamber
specification: TD-12/1600-31.5 Ceramic vacuum arc extinguishing chamber
  Zoom Zoom in on the image
Category: spare parts and accessories -- Ceramic arc extinguishing chamber
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


TD-12/1600-31.5 Ceramic vacuum arc extinguishing chamberDetailed product description:Column tabs
Overview

The ceramic vacuum arc extinguishing chamber for TD-12/1600-31.5 circuit breaker adopts corrugated ceramic as the insulation shell, with CuCr50 alloy contacts and cup-shaped longitudinal magnetic structure. It has the characteristics of large current interruption, high insulation level, strong arc extinguishing ability, long service life, small size, simple maintenance, no explosion hazard, no pollution, and low noise. The indoor vacuum circuit breaker assembled with it is used for control and protection in the transmission and distribution systems of power, machinery, chemical, metallurgical, mining, railway and other departments, and is suitable for places with frequent operations.

Main technical parameters of ceramic vacuum arc extinguishing chamber for TD-12/1600-31.5 circuit breaker

Parameter name

Unit Unit

Numerical Value

Rated voltage

kV

twelve

Rated normal current

A

one thousand and six hundred

Rated short-circuit breaking current
Rated short-circuit breaking current

kA

thirty-one point five

Rated short circuit making current

kA

eighty

Rated peak withstand current

kA

eighty

Rated short-time withstand current

kA

thirty-one point five

Rated duration of short circuit

S

four

Rated breaking current of a single capacitor bank
Rated single capacitor unit breaking current

A

six hundred and thirty

Rated back-to-back capacitor bank breaking current
Rated back to back capacitor unit breaking current

A

four hundred

Rated short-time (1min) power frequency withstand voltage
Rated short time power frequency withstand voltage (1min)

kV

forty-two

Circuit resistance under rated contact pressure
Circuit resistance at lower limit of rated contact pressure

μΩ

≤30

Rated short-circuit breaking current breaking times
Rated short circuit breaking current breaking times

time

Time

thirty

Rated lightning impulse withstand voltage
Rated lightning impulse withstand voltage

kV

seventy-five

mechanical life
Mechanical endurance

Next Time

ten thousand

Closing force due to bellows and atmosphere

N

120±50

Contact reaction force at rated opening distance
Force required to hold contacts open at full stroke

N

200±50

Contact wear allowance thickness

mm

three

Internal gas pressure

Pa

≤1.33×10ˉthree

Allow storage period

Year of Year

twenty



Mechanical parameters for using circuit breakers

Project

Unit Unit

Numerical Value

Contact stroke distance

mm

11±1

Contact travel

mm

one0

Average closing speed

m/s

0.6±0.2

Average opening speed

m/s

1.1±0.2

Rated contact pressure

N

3100±200

Contact closing bounce time

ms

≤2

Out of simultaneity of contact closing and opening

ms

≤2

Bouncing back amplitude of opening contact

mm

≤2

Installation dimensions of ceramic vacuum arc extinguishing chamber for TD-12/1600-31.5 circuit breaker
Ceramic vacuum arc extinguishing chamber for TD-12/1600-31.5 circuit breaker

TD-12/1600-31.5 Ceramic vacuum arc extinguishing chamber
Product Category