BD-40.5/1250-25 Glass vacuum arc extinguishing chamberDetailed product description:Column tabs
Overview
The glass vacuum arc extinguishing chamber for circuit breaker BD-40.5/1250-25 adopts a medium sealed structure, glass shell, CuCr50 alloy contacts, cup-shaped longitudinal magnetic structure, with the characteristics of large current breaking capacity, high insulation level, strong arc extinguishing ability, long service life, small volume, simple maintenance, no explosion hazard, no pollution, low noise, etc. The outdoor vacuum circuit breaker assembled with it is used for control and protection in power transmission and distribution systems such as industrial and mining, enterprises, and substations.

Main technical parameters of glass vacuum arc extinguishing chamber for circuit breaker BD-40.5/1250-25

Parameter name

Unit Unit

Numerical Value

Rated voltage

kV

forty point five

Rated normal current

A

one thousand two hundred and fifty

Rated short-circuit breaking current
Rated short-circuit breaking current

kA

twenty-five

Rated short circuit making current

kA

fifty

Rated peak withstand current

kA

fifty

Rated short-time withstand current

kA

twenty-five

Rated duration of short circuit

S

four

Rated breaking current of a single capacitor bank
Rated single capacitor unit breaking current

A

six hundred and thirty

Rated back-to-back capacitor bank breaking current
Rated back to back capacitor unit breaking current

A

four hundred

Rated short-time (1min) power frequency withstand voltage
Rated short time power frequency withstand voltage (1min)

kV

ninety-five

Circuit resistance under rated contact pressure
Circuit resistance at lower limit of rated contact pressure

μΩ

≤30

Rated short-circuit breaking current breaking times
Rated short circuit breaking current breaking times

time

Time

twenty

Rated lightning impulse withstand voltage
Rated lightning impulse withstand voltage

kV

one hundred and eighty-five

Mechanical endurance

Next Time

ten thousand

Contact self closing force
Closing force due to bellow and atmosphere

N

250±50

Contact reaction force at rated opening distance
Force required to hold contacts open at full stroke

N

330±60

Contact wear allowance thickness

mm

three

Internal gas pressure

Pa

≤1.33×10ˉthree

Allow storage period

Year of Year

twenty


Mechanical parameters for using circuit breakers

Project

Unit Unit

Numerical Value

Contact stroke distance

mm

22±2

Contact travel

mm

8±2

Average closing speed

m/s

0.6±0.2

Average opening speed

m/s

1.4±0.2

Rated contact pressure

N

2900±300

Contact closing bounce time

ms

≤2

Non synchronous closing and opening of contacts
Out of simultaneity of contact closing and opening

ms

≤2


Outline dimensions of glass vacuum arc extinguishing chamber for circuit breaker BD-40.5/1250-25
Glass vacuum arc extinguishing chamber for circuit breaker BD-40.5/1250-25

BD-40.5/1250-25 Glass vacuum arc extinguishing chamber
Product Category