| Product name: | TF-40.5/1250-20 Ceramic arc extinguishing chamber | ||||||
| specification: | ![]() |
||||||
| Category: | spare parts and accessories -- Ceramic arc extinguishing chamber | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
Parameter name |
Unit Unit |
Parameter Value |
|
Rated voltage |
kV |
forty point five |
|
Rated current |
A |
one thousand two hundred and fifty |
|
Rated frequency |
Hz |
50/60 |
|
Short term (1-minute) power frequency withstand voltage |
kV |
seventy |
|
Lightning impulse withstand voltage |
kV |
one hundred and seventy |
|
Rated short-circuit breaking current |
kA |
twenty |
|
Rated peak withstand current |
kA |
fifty |
|
Rated short-circuit closing current |
kA |
fifty |
|
Rated short-time withstand current |
kA |
twenty |
|
Rated short-circuit duration |
S |
four |
|
Rated breaking current of a single capacitor bank |
A |
six hundred and thirty |
|
Rated back-to-back capacitor bank breaking current |
A |
four hundred |
|
mechanical life |
Next time |
ten thousand |
|
Contact self closing force |
N |
60±20 |
|
Contact reaction force at rated opening distance |
N |
145±20 |
|
Contact limit abrasion thickness allowed for contacts |
mm |
three |
|
Gas pressure inside the vacuum arc extinguishing chamber |
Pa |
≤1.33×10ˉthree |
|
Weight of moving parts |
kg |
zero point four five |
|
Quality of vacuum arc extinguishing chamber |
kg |
one point two |
|
Clearance between open contacts |
mm |
15±1 |
|
Average opening speed |
m/s |
1.6±0.2 |
|
Average closing speed |
m/s |
0.8±0.2 |
|
Rated contact force |
N |
700±100 |
|
Contact closing bounce time |
ms |
≤2 |
|
Non synchronous closing and opening of contacts |
ms |
≤2 |
|
Rebound amplitude of the opening contact |
mm |
≤2 |

Ceramic arc extinguishing chamber for TF-40.5/1250-20 load switch