HomeYour location:Homespare parts and accessoriesvacuum interrupterCeramic arc extinguishing chamber → TF-40.5/1250-20 Ceramic arc extinguishing chamber
Column tabs 
Product name: TF-40.5/1250-20 Ceramic arc extinguishing chamber
specification: TF-40.5/1250-20 Ceramic arc extinguishing chamber
  Zoom Zoom in on the image
Category: spare parts and accessories -- Ceramic arc extinguishing chamber
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


TF-40.5/1250-20 Ceramic arc extinguishing chamberDetailed product description:Column tabs
Overview
The ceramic arc extinguishing chamber for TF-40.5/1250-20 load switch adopts a ceramic insulation shell, low current cutoff value, and long-life Wcu contact material, which has the advantages of strong arc extinguishing ability, reliable performance, long life, small size, no explosion hazard, and no environmental pollution The corresponding vacuum automatic switch can be used for control and protection of transmission and distribution systems in power, metallurgy, mining, chemical and other departments, especially suitable for places that require frequent operation. Product Description

Main technical parameters of ceramic arc extinguishing chamber for TF-40.5/1250-20 load switch

Parameter name

Unit Unit

Parameter Value

Rated voltage

kV

forty point five

Rated current

A

one thousand two hundred and fifty

Rated frequency

Hz

50/60

Short term (1-minute) power frequency withstand voltage
Short time power frequency withstand voltage (1min)

kV

seventy

Lightning impulse withstand voltage
Lightning impulse withstand voltage

kV

one hundred and seventy

Rated short-circuit breaking current
Rated short circuit breaking current

kA

twenty

Rated peak withstand current
Rated peak withstand current

kA

fifty

Rated short-circuit closing current
Rated short circuit making current

kA

fifty

Rated short-time withstand current
Rated short time withstand current

kA

twenty

Rated short-circuit duration
Rated duration of short circuit

S

four

Rated breaking current of a single capacitor bank
Rated breaking current of single capacitor bank

A

six hundred and thirty

Rated back-to-back capacitor bank breaking current
Rated breaking current of back to back capacitor bank

A

four hundred

mechanical life
Mechanical endurance

Next time

ten thousand

Contact self closing force
Closing force due to bellow and atmosphere

N

60±20

Contact reaction force at rated opening distance
Force required to hold contacts open at full stroke

N

145±20

Contact limit abrasion thickness allowed for contacts

mm

three

Gas pressure inside the vacuum arc extinguishing chamber
Gas pressure inside vacuum interrupter

Pa

≤1.33×10ˉthree

Weight of moving parts

kg

zero point four five

Quality of vacuum arc extinguishing chamber
Weight of vacuum interrupter

kg

one point two


Mechanical parameters of load switch

Clearance between open contacts

mm

15±1

Average opening speed

m/s

1.6±0.2

Average closing speed

m/s

0.8±0.2

Rated contact force

N

700±100

Contact closing bounce time
Contact bouncing duration at closing operation

ms

≤2

Non synchronous closing and opening of contacts
Out of simultaneity of contact closing and opening

ms

≤2

Rebound amplitude of the opening contact
Bouncing back amplitude of opening contact

mm

≤2


External dimensions of ceramic arc extinguishing chamber for TF-40.5/1250-20 load switch
Ceramic arc extinguishing chamber for TF-40.5/1250-20 load switch

TF-40.5/1250-20 Ceramic arc extinguishing chamber
Product Category