| Product name: | TD-12/630-25 Ceramic vacuum arc extinguishing chamber | ||||||
| specification: | ![]() |
||||||
| Category: | spare parts and accessories -- Ceramic arc extinguishing chamber | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
Parameter name |
Unit Unit |
Numerical Value |
|
Rated voltage |
kV |
twelve |
|
Rated current |
A |
six hundred and thirty |
|
Rated frequency |
Hz |
fifty |
|
Short term (1-minute) power frequency withstand voltage |
kV |
forty-two |
|
Lightning impulse withstand voltage |
kV |
seventy-five |
|
Rated short circuit breaking current |
kA |
twenty-five |
|
Rated peak withstand current |
kA |
sixty-three |
|
Rated short circuit making current |
kA |
sixty-three |
|
Rated short time withstand current |
kA |
twenty-five |
|
Rated duration of short circuit |
S |
four |
|
Rated breaking current of a single capacitor bank |
A |
six hundred and thirty |
|
Rated back-to-back capacitor bank breaking current |
A |
four hundred |
|
Rated short-circuit breaking current times |
Next time |
thirty |
|
mechanical life |
Next time |
ten thousand |
|
Contact self closing force |
N |
140±50 |
|
Contact reaction force at rated opening distance |
N |
230±50 |
|
Circuit resistance at lower limit of rated contact pressure |
μΩ |
≤25 |
|
Allowable wear thickness of contacts |
mm |
three |
|
Gas pressure inside the vacuum arc extinguishing chamber |
Pa |
≤1.33×10ˉthree |
|
Quality of the sports section |
kg |
one point three |
|
Quality of vacuum arc extinguishing chamber |
kg |
four point two |
|
Clearance between open contacts |
mm |
11±1 |
|
Average opening speed |
m/s |
1.1±0.2 |
|
Average closing speed |
m/s |
0.6±0.2 |
|
Rated contact force |
N |
2000±200 |
|
Contact closing bounce time |
ms |
≤2 |
|
Non synchronous closing and opening of contacts |
ms |
≤2 |
|
Rebound amplitude of the opening contact |
mm |
≤3 |

Ceramic vacuum arc extinguishing chamber for TD-12/630-25 circuit breaker