parameter name Parameter name |
unit Unit |
numerical value Value |
|
Rated voltage |
kV |
twelve |
|
Rated current |
A |
six hundred and thirty |
|
Rated frequency |
Hz |
fifty |
|
Short term (1-minute) power frequency withstand voltage |
kV |
forty-two |
|
Lightning impulse withstand voltage |
kV |
seventy-five |
|
Rated short circuit breaking current |
kA |
twelve point five |
|
Rated peak withstand current |
kA |
thirty-one point five |
|
Rated short circuit making current |
kA |
thirty-one point five |
|
Rated short time withstand current |
kA |
twelve point five |
|
Rated duration of short circuit |
S |
four |
|
Rated breaking current of a single capacitor bank |
A |
six hundred and thirty |
|
Rated back-to-back capacitor bank breaking current |
A |
four hundred |
|
Rated short circuit breaking current times |
Next time |
thirty |
|
Mechanical endurance |
time |
ten thousand |
|
Closing force due to bellows and atmosphere |
N |
60±30 |
|
Force required to hold contacts open at full stroke at rated opening distance |
N |
160±30 |
|
Circuit resistance at lower limit of rated contact force |
μΩ |
≤35 |
|
Contact limit abrasion |
mm |
three |
|
Gas pressure inside vacuum interrupter |
Pa |
≤1.33×10ˉthree |
|
Weight of moving parts |
kg |
zero point three five |
|
Weight of vacuum interrupter |
kg |
one point two |
|
Clearance between open contacts |
mm |
8±1 |
|
Average opening speed |
m/s |
1.2±0.2 |
|
Average closing speed |
m/s |
0.8±0.2 |
|
Rated contact force |
N |
1200±200 |
|
Contact bounce duration at closing operation |
ms |
≤2 |
|
Out of simultaneity of contact closing and opening |
ms |
≤2 |
|
Bouncing back amplitude of opening contact |
mm |
≤2 |

Ceramic vacuum arc extinguishing chamber for TD-12/630-12.5 circuit breaker