| Product name: | BD-12/1250-25 Glass vacuum arc extinguishing chamber | ||||||
| specification: | ![]() |
||||||
| Category: | spare parts and accessories -- Glass arc extinguishing chamber | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
Parameter Name Parameter name |
unit Unit |
numerical value Value |
|
rated voltage Rated voltage |
kV |
twelve |
|
rated current Rated normal current |
A |
one thousand two hundred and fifty |
|
Rated short-circuit breaking current Rated short-circuit breaking current |
kA |
twenty-five |
|
Rated short-circuit closing current Rated short-circuit making current |
kA |
sixty-three |
|
Rated peak withstand current Rated peak withstand current |
kA |
sixty-three |
|
Rated short-time withstand current Rated short-time withstand current |
kA |
twenty-five |
|
Rated short-circuit duration Rated duration of short circuit |
S |
four |
|
Rated breaking current of a single capacitor bank Rated single capacitor unit breaking current |
A |
six hundred and thirty |
|
Rated back-to-back capacitor bank breaking current Rated back to back capacitor unit breaking current |
A |
four hundred |
|
Rated short-time (1min) power frequency withstand voltage Rated short time power frequency withstand voltage (1min) |
kV |
forty-two |
|
Circuit resistance under rated contact pressure Circuit resistance at lower limit of rated contact pressure |
μΩ |
≤30 |
|
Rated short-circuit breaking current breaking times Rated short circuit breaking current breaking times |
time time |
thirty |
|
Rated lightning impulse withstand voltage Rated lightning impulse withstand voltage |
kV |
seventy-five |
|
mechanical life Mechanical endurance |
time time |
ten thousand |
|
Contact self closing force Closing force due to bellow and atmosphere |
N |
120±50 |
|
Contact reaction force at rated opening distance Force required to hold contacts open at full stroke |
N |
200±50 |
|
Allowable wear thickness of contacts Contact-wear allowance thickness |
mm |
three |
|
Internal gas pressure Internal gas pressure |
Pa |
≤1.33×10ˉthree |
|
Allowable storage period Storage period |
year year |
twenty |
|
project Project |
unit Unit |
numerical value Value |
|
contact gap Contact stroke |
mm |
11±1 |
|
Contact stroke of contacts Contact travel |
mm |
3.5±0.5 |
|
Average closing speed Average closing speed |
m/s |
0.6±0.2 |
|
Average opening speed Average opening speed |
m/s |
1.1±0.2 |
|
Rated contact pressure Rated contact pressure |
N |
2500±200 |
|
Contact closing bounce time Contact closing bounce time |
ms |
≤2 |
|
Non synchronous closing and opening of contacts Out of simultaneity of contact closing and opening |
ms |
≤2 |

Glass vacuum arc extinguishing chamber for circuit breaker BD-12/1250-25