| Product name: | TD-24/2000, TD-24/2500-31.5 Vacuum arc extinguishing chamber | ||||||
| specification: | ![]() |
||||||
| Category: | spare parts and accessories -- Ceramic arc extinguishing chamber | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
serial number |
name |
unit |
Numerical value |
|
one |
rated voltage |
kV |
twenty-four |
|
two |
rated current |
A |
2000/2500 |
|
three |
rated frequency |
HZ |
fifty |
|
four |
Short term (1-minute) power frequency withstand voltage |
kV |
sixty-five |
|
five |
Lightning impulse withstand voltage (peak value) |
kV |
eighty-five |
|
six |
Rated short-circuit breaking current |
kA |
forty |
|
seven |
Rated peak withstand current |
kA |
eighty |
|
eight |
Rated short-circuit closing current |
kA |
eighty |
|
nine |
Rated short-time withstand current (4 seconds) |
kA |
thirty-one point five |
|
ten |
Rated short-circuit duration |
s |
four |
|
eleven |
Rated breaking current of a single capacitor bank |
A |
six hundred and thirty |
|
twelve |
Rated back-to-back capacitor bank breaking current |
A |
four hundred |
|
thirteen |
Rated short-circuit breaking current breaking times |
time |
thirty |
|
fourteen |
mechanical life |
time |
ten thousand |
|
fifteen |
Circuit resistance under rated contact pressure |
μΩ |
≤15 |
|
sixteen |
Contact self closing force |
N |
200±60 |
|
seventeen |
Contact reaction force at rated opening distance |
N |
300±60 |
|
eighteen |
Allowable wear thickness of contacts |
mm |
three |
|
nineteen |
Gas pressure inside the vacuum arc extinguishing chamber |
Pa |
≤1.33×10-3 |
|
twenty |
Quality of the sports section |
kg |
one point two |
|
one |
contact gap |
mm |
10±1.0 |
|
two |
Average opening speed |
m/s |
1.2±0.2 |
|
three |
Average closing speed |
m/s |
0.7±0.2 |
|
four |
Contact closing bounce time |
ms |
≤2 |
|
five |
Rated contact pressure |
N |
4200±200 |
|
six |
Contact closing and opening at different periods |
ms |
≤1 |
|
seven |
Contact rebound amplitude |
mm |
≤1.5 |
|
eight |
Contact stroke of contacts |
mm |
3+one0 |

Vacuum arc extinguishing chamber for circuit breakers TD-24/2000, TD-24/2500-31.5