purpose
DZ-200X intermediate relay is used in various protection and automatic control devices to increase the number and capacity of contacts in protection and control circuits.
model

Comparison Table of Contact Forms for DZY, DZL, and DZJ:
Table 1
|
Contact Number |
01 |
02 |
03 |
04 |
05 |
06 |
07 |
08 |
09 |
ten |
eleven |
|
contact form |
002 |
006 |
two hundred and two |
two hundred and twenty |
two hundred and forty |
four hundred |
four hundred and two |
four hundred and twenty |
six hundred |
six hundred and two |
six hundred and twenty |
|
Contact Number |
twelve |
thirteen |
fourteen |
fifteen |
sixteen |
seventeen |
eighteen |
nineteen |
twenty |
twenty-one |
twenty-two |
|
contact form |
eight hundred |
004 |
060 |
062 |
080 |
two hundred and forty-two |
two hundred and sixty |
four hundred and twenty-two |
four hundred and forty |
024 |
two hundred and four |
Comparison Table of Contact Forms for DZB, DZS, and DZK: Table 2
|
Contact Number |
one |
two |
three |
four |
five |
six |
seven |
eight |
nine |
|
contact form |
002 |
006 |
two hundred and two |
two hundred and twenty |
two hundred and forty |
four hundred |
four hundred and two |
four hundred and twenty |
six hundred |
Appendix: Classification of DZB, DZK, DZS Functions
DZB model classification:
1. One voltage winding and one current winding can both serve as working windings and holding windings;
2. One voltage working winding and two current holding windings;
3. One voltage working winding, two current holding and damping windings, fixed short circuited damping windings, with an action time of 0.06 seconds or more;
4. One voltage working winding, two current holding and damping windings, and a variable connection of the group winding. When the damping winding is not short circuited, the action time is below 0.045s, and when short circuited, the action time is above 0.06s;
5. One voltage working winding and four current holding windings;
6. One voltage working winding, four current holding and damping windings, and variable connection of damping windings. When the damping winding is not short circuited, the action time is below 0.045s, and when short circuited, the action time is above 0.06s;
7. One current working winding, one voltage holding winding, and one damping winding, with variable connection of the damping winding. When the damping winding is short circuited, the return time is more than 0.5s;
8. One current working winding, one current holding winding, and one voltage holding winding, with an action time of less than 0.03s.
DZK model classification:
1. A voltage working winding with an action time of less than 0.015s;
2. One voltage working winding, two current holding windings, with an action time of less than 0.015s;
3. One voltage working winding, three current holding windings, with an action time of less than 0.015s;
4. One voltage working winding and one voltage holding winding (with additional resistance).
DZS model classification:
1. Action delay: 0.06s or more;
2. Action delay: 0.11s or more;
3. Return delay: 0.5 seconds or more;
4. Return delay: 1.1s or more;
5. Return delay: 0.4 seconds or more when the damping winding is not short circuited, and 0.8 seconds or more when the damping winding is short circuited;
Note: DZY and DZJ are voltage working windings; DZL is a current working winding; DZK voltage windings must be connected to external resistors.
Main technical data
Rated voltage: DC 220V, 110V, 48V, 24V;
AC 380V, 220V, 127V, 110V, 100V, 60V, 48V, 36V, 12V.
Rated current: 0.25A, 0.5A, 1A, 2A, 4A, 8A.
Action value and holding value: a. The action voltage and holding voltage shall not exceed 70% of the rated voltage, and the action voltage of DZJ-200 shall not exceed 80% of the rated voltage and not be less than 30% of the rated voltage; DZK-200 and DZB-243 shall not be less than 50% of the rated voltage.
b. The operating current and holding current shall not exceed 80% of the rated voltage.
Return value: not less than 5% of the rated value. DZB-200 and DZS-200 shall not be less than 3% of the rated value.
Power consumption: not exceeding 5W.
Contact capacity: In a DC inductive load circuit with a voltage not exceeding 250V, a current not exceeding 5A, and a time constant of 5 ± 0.75ms, the output contact of the product has a breaking capacity of 50W. Under the specified load conditions, the output contact of the product can reliably operate and return 5 × 104 times. The long-term allowable current for the output contact is 5A.
Dielectric strength: When the conductive terminals of the product are connected together, it can withstand an AC voltage of 2000V (effective value) 50Hz for 1 minute without insulation breakdown or flashover between exposed non charged metal parts or shells.
DZK external resistance value
|
Specification (V) |
two hundred and twenty |
one hundred and ten |
forty-eight |
twenty-four |
|
External resistance value (Ω) |
five thousand and one hundred |
one thousand and two hundred |
two hundred and twenty |
fifty-six |
Internal wiring diagram