| Product name: | CSM005A series Hall current sensor | ||||||
| specification: | ![]() |
||||||
| Category: | low-voltage electrical apparatus -- current sensor | ||||||
| Price: | factory price | ||||||
| Brand: | 奇霍 | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
model |
CSM001A |
CSM002A |
CSM003A |
CSM005A |
||
|
IPN |
Primary rated input current |
one |
two |
three |
five |
A |
|
IP |
Measurement range of primary current |
0~±2 |
0~±4 |
0~±6 |
0~±10 |
A |
|
ISN |
Rated output current on the secondary side |
twenty-five |
twenty-five |
twenty-five |
twenty-five |
mA |
|
KN |
turns ratio |
25:1000 |
12:960 |
8:960 |
5:1000 |
|
|
RM |
Measure resistance (VC=± 15V) |
±IPN max 100~460 |
±IP max 100~205 |
Ω | ||
|
VC |
power supply voltage |
±12~±15(±5%) |
V | |||
|
IC |
Current consumption |
VC=±15V 10+Is |
mA | |||
|
Vd |
insulation voltage |
2.5KV effective value/50Hz/1 minute between the primary and secondary circuits |
||||
|
εL |
linearity |
<0.2 |
%FS | |||
|
XG |
precision |
TA =25℃ VC=±15V ±0.7 |
% | |||
|
I0 |
Zero offset current |
TA =25℃ <±0.15 |
mA | |||
|
IOM |
Magnetic misalignment current |
IP→0 <±0.15 |
mA | |||
|
IOT |
Imbalance current temperature drift |
IP=0 TA =-25~+85℃ <±0.5 |
mA | |||
|
Tr |
response time |
<1 |
μs | |||
|
f |
Band width (-1dB) |
DC~100 |
kHz | |||
|
TA |
Working environment temperature |
-25~+85 |
℃ | |||
|
TS |
Storage environment temperature |
-40~+100 |
℃ | |||
|
RS |
Internal resistance of secondary coil |
TA =85℃ 50 |
Ω | |||
|
standard |
Q/3201CHGL02-2007 |
|||||
Dimensions (mm)
Instructions for Use
1. Incorrect wiring of sensors may result in module damage. After the sensor is powered on, when the measured current passes through the direction of the sensor arrow, the in-phase current value can be measured at the output terminal.
2. Sensors with different rated input currents and output voltages can be customized according to user needs.