CS1000F series Hall current sensorDetailed product description:Column tabs
The CS1000F series Hall current sensor applies the open-loop principle of Hall effect to measure DC, AC, pulse, and various other currents under electrically isolated conditions
Irregular waveform current.

CS1000F series Hall current sensor electrical parameters

model
CS100F
CS200F
CS400F
CS600F
CS800F
CS1000F
IPN
Primary rated input current
one hundred
two hundred
four hundred
six hundred
eight hundred
one thousand
A
IP
Measurement range of primary current
0~±200
0~±400
0~±800
0~±1200
0~±1600
0~±2000
A
VOUT
Rated output voltage on the secondary side
4±1%
V
VC
power supply voltage
±12~±15(±5%)
V
IC
current consumption
VC=±15V <25
mA
Vd
insulation voltage
5KV effective value/50Hz/1 minute between the primary and secondary circuits
εL
linearity
<1
%FS
V0
Zero offset voltage
TA =25℃ <±25
mV
VOM
Magnetic misalignment voltage
IPN→0 <±25
mV
VOT
Unbalanced voltage temperature drift
IP=0 TA =-25~+85℃ <±1
mV/℃
Tr
response time
≤7
μs
f
Band width (-3dB)
DC~20
kHz
TA
Working environment temperature
-25~+85
TS
Storage environment temperature
-40~+100
RL
load resistor
≥10K
Ω

Dimensions (mm)

Installation dimensions of CS1000F series Hall current sensor

Pin output: 1,+15V 2, -15V 3, Vout 4, 0V (power ground) OFS, zero adjustment GIN, amplitude adjustment
Lead output: red,+15V blue, -15V yellow, Vout black, 0V (power ground)

Instructions for Use
1. Incorrect wiring may cause damage to the sensor. After the sensor is powered on, when the measured current passes through the direction of the sensor arrow, the in-phase voltage value can be measured at the output terminal.
2. The output amplitude of the sensor can be adjusted appropriately according to user needs.
3. Sensors with different rated input currents and output voltages can be customized according to user needs

CS1000F series Hall current sensor
Product Category