| Product name: | JGJ19 Modular single-phase AC solid-state relay | ||||||
| specification: | ![]() |
||||||
| Category: | low-voltage electrical apparatus -- solid state relay | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
| model | JGJ19 (formerly JGX9) | |
| lose enter ginseng number |
control voltage | 3~32 VDC 4~24 VDC |
| control the current | ≤25 mA | |
| starting current | ≥6 mA | |
| Turn off voltage | ≤1.5VDC | |
| On-off time | ≤20mS | |
| lose exit ginseng number |
load voltage | 24~240VAC 24~440VAC 24~660VAC |
| Maximum load current | 60、80、90、100、120A 150、180、200、250、300A 350、400、500、600A | |
| On state pressure drop | ≤1.8V | |
| Off state voltage | ≥400V ≥ 800V ≥ 1500V | |
| sex can ginseng number |
isolation voltage | ≥2500V |
| insulation voltage | ≥2500V | |
| insulation resistance | ≥100MΩ | |
| Operating Temperature | —25~75 ℃ | |
| power frequency | 50/60HZ | |
| heat dissipation conditions | ≥ 20A with radiator, ≥ 40A with fan for strong cooling | |
| Load current safety factor | Resistive load is taken as 2-3 times, inductive load is taken as 3-4 times | |
| External dimensions (code) | 94×25×31(M-1) 94×34×32(M-2) 120×52×32(M-3) | |
JGJ19 Modular Single phase AC Solid State Relay Dimensions Installation wiring diagram: (unit: mm)