| Product name: | NHR17 series fuse type isolating switch | ||||||
| specification: | ![]() |
||||||
| Category: | low-voltage electrical apparatus -- Knife melting switch | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||

|
Distribution fuse size |
00 |
one |
two |
three | ||||||||
|
Power supply, frequency |
AC、50Hz |
AC、50Hz |
AC、50Hz |
AC、50Hz | ||||||||
|
Rated voltage (V) |
six hundred and ninety |
five hundred |
four hundred |
six hundred and ninety |
five hundred |
four hundred |
six hundred and ninety |
five hundred |
four hundred |
six hundred and ninety |
five hundred |
four hundred |
|
Rated insulation voltage (V) |
eight hundred |
eight hundred |
eight hundred |
eight hundred | ||||||||
|
Power frequency withstand voltage (V) |
three thousand |
three thousand |
three thousand |
three thousand | ||||||||
|
Rated working current (A) |
one hundred and sixty |
two hundred and fifty |
four hundred |
six hundred and thirty | ||||||||
|
Agreed heating current (A) |
one hundred and sixty |
two hundred and fifty |
four hundred |
six hundred and thirty | ||||||||
|
Usage category |
AC-21B(690V) |
AC-21B(690V) |
AC-21B(690V) |
AC-21B(690V) | ||||||||
|
AC-22B(500V) |
AC-22B(500V) |
AC-22B(500V) |
AC-22B(500V) | |||||||||
|
AC-23B(400V) |
AC-23B(400V) |
AC-23B(400V) |
AC-23B(400V) | |||||||||
|
Rated connection capacity |
725V、240A |
725V、375A |
725V、69OA |
725V、945A | ||||||||
|
525V、480A |
|
525V、1200A |
525V、1890A | |||||||||
|
420V、1600A |
420V、2500A |
420V、4000A |
420V、6300A | |||||||||
|
Rated breaking capacity |
725V、240A |
725V、375A |
725V、69OA |
725V、945A | ||||||||
|
525V、480A |
525V、750A |
525V、1200A |
525V、1890A | |||||||||
|
420V、1280 |
420V、2000A |
420V、3200A |
420V、5040A | |||||||||
|
Rated short-circuit current (KA) |
fifty |
one hundred |
one hundred |
fifty |
one hundred |
one hundred |
fifty |
one hundred |
one hundred |
fifty |
one hundred |
one hundred |
|
Loss power of fuse (W) |
twelve |
twenty-three |
thirty-four |
forty-eight | ||||||||
|
The agreed heating current (A) |
Fuse size |
Acceptable melt current value (A) |
|
one hundred and sixty |
00 |
4. 6, 10, 16, 20, 25, 32, 35, 40, 50, 63, 80, 10, 125, 160 |
|
two hundred and fifty |
one |
80, 100, 125, 160, 200, 224, 250 |
|
four hundred |
two |
125, 160, 200, 224, 250, 300, 315, 355, 400 |
|
six hundred and thirty |
three |
315, 355, 400, 425, 500, 630 |
Note: When a switch is used in an electric motor circuit, the rated current of the fuse is allowed to be greater than the agreed heating current of the switch.