LZK-10W outdoor open type current transformer is used for current measurement, protection, control, etc. of medium voltage overhead lines of 10kV and below. It does not require wire cutting during installation and can also be installed live.
Current monitoring and control of automatic reactive power compensation device for 10kV overhead power lines. It has the characteristics of arc resistance, UV resistance, aging resistance, and long maintenance free cycle.
LZK-10W Outdoor Open Current Transformer Technical Data
Rated insulation level: 12/42/75kV
Rated frequency: 50Hz or 60Hz
Surface creepage distance: 460mm
Primary wire cross-section: 35-400mm2
Environmental temperature: -30 ℃~+55 ℃, daily average not exceeding+40 ℃
Altitude: not exceeding 3000 meters.
Table 1 Rated primary and secondary currents, accuracy levels, and corresponding secondary output capacities
Primary current (A) | Secondary output | Rated capacity (VA) | accuracy level | Maximum Capacity (VA) |
100~200 | 1A or 5A | two point five | ±0.5% | five |
300~400 | five | zero point five | ten |
500~750 | five | zero point two | twenty |
100~750 | 10V | | 0.2~0.5 | |
Installation steps:
1. Fix the current transformer and its base on the crossbar, and install the transformer protection box vertically to avoid water ingress or storage inside the box.
2. Determine the position of the current transformer clamp wire, wrap the high-voltage wire at this position with insulating tape, with a length of about 390 millimeters and a diameter of about 22 millimeters after winding.
3. Wrap the wire around the winding part with an insulating sleeve, and then wrap a layer of insulating tape (about 1mm) outside the sleeve
4. Place the overhead wire with conduit installed in the center of the current transformer, symmetrically in front and behind.
5. Apply silicone evenly on the joint surface of the upper and lower halves of the current transformer, align and fix them together.
6. Wrap the metal braided wire on the CT with a primary wire using metal binding wire to maintain equipotential.
7. Place the protective cover over the CT and fasten 10 buttons.
Attention: Install a lightning arrester next to the LZK-10W current transformer to prevent lightning strikes.