| Product name: | DXN-8B series indoor high-voltage live display device voltage indicator | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- live display | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
The voltage indicator of the DXN-8B series indoor high-voltage live display device is equipped with self check and power verification buttons on the panel. The three-phase indicator lights can only light up when the self check or power verification button is pressed when the usage conditions are met (see display device functions for details), which can greatly improve the service life of the light-emitting components. Due to the use of low-power light-emitting components in its internal circuit, the overall power consumption of the machine is low, the performance is more stable, and the reliability is higher. For the convenience of users to verify the phase of dual power sources on site, the indicator panel is equipped with a phase test terminal. At the same time, the front frame of the indicator housing is detachable, and users can replace the indicator light without opening the indicator housing on site. It is widely used in indoor high-voltage electrical equipment with 3.6, 7.2, 12, 24, 40.5kV, and frequency 50Hz, and can be used in conjunction with voltage sensors to reflect the high voltage live status. It can also be used in conjunction with isolation switches and grounding switches to improve the anti misoperation performance of supporting products.
Normal working conditions for voltage indicator of DXN-8B series indoor high-voltage live display device:
Environmental temperature:+40 ℃~-25 ℃;
Sea level altitude: not exceeding 2000m;
The daily average relative humidity of the environment shall not exceed 95%,
The monthly average is not greater than 90%.
○ Display device (voltage indicator) model meaning and function;
AB-DXN 8B - mouth/mouth mouth mouth mouth mouth mouth mouth mouth
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨
① Indoor high-voltage live display device ② Design number
③ Rated voltage level ④ Indicator specification T: Prompt type indicator Q: Lock type indicator
⑤ S: The light-emitting diode flashes and emits light; Not specified indicates that the LED is constantly on and emitting light
⑥ K: Panel setting indicator light stop switch; Not specified means without switch
⑦ 2: "One to Two" Plan; Not specified indicates a solution of one sensor with one indicator
⑧ B: Equipped with a black phase detector; Y: The colors at the verification end are yellow, green, and red; Not specified indicates no phase testing end
⑨ X1.0: Equipped with regular wires; PX1.0: Equipped with shielded wire; Not specified indicates no wiring
(1.0 indicates a 1M wire, and the length of the wire can be determined according to customer requirements)
Product volume and opening size
1. Volume: 120X80X65mm
2. Hole size: 100.5X70.5mm
Function of the power verification button:
1. When the high voltage side is powered off, press the power test button, and the A, B, and C indicator lights that display high voltage live should not light up;
2. When the voltage at the high voltage end reaches 15%~<65% of the rated phase voltage, press the power test button, and the A, B, and C indicator lights that display high voltage charging will begin to indicate the charging status of the high voltage end respectively; (See Figure 2 for the wiring diagram used in conjunction with the voltage sensor).
In addition to the above functions, the Q-type voltage indicator can also achieve the following: when any phase voltage in the three-phase high-voltage bus reaches 65%~100% of the rated phase voltage, the electronic circuit control relay output contact J opens and is in a forced locking state;
(Rear view of terminals 3, 4 or K1, K2 in the wiring diagram). When all three phases are not charged, ① the secondary working power supply is normal, the output contact is closed, and it is in an unlocked state;
② The secondary working power supply is disconnected, the output contact is open, and it is in a protective locking state.
Note: Status 3 and 4 belong to the indicator protection state. When the indicator loses its working power supply, regardless of whether there is voltage at the high voltage end, the relay will be locked
The output contact is always in the disconnected position.
This device is for informational purposes only. Staff must strictly comply with electrical safety operating procedures when entering live compartments.
matters needing attention:
The 2000V/1-minute withstand voltage cannot be applied between the input terminals a, b, c of the indicator signal and the ground (because a, b, c and
The working circuit has been formed between the grounding points through the indicator light, otherwise the indicator will be damaged.
The parts where the indicator can perform a 2000V/1-minute test are: ① parallel connection of the power input terminal to ground; ② Relay contacts are connected in parallel to ground.
DXN-8B series indoor high-voltage live display device voltage indicator