The CW3DC DC universal circuit breaker (hereinafter referred to as the circuit breaker) maintains the same external dimensions and installation dimensions as the CW3. It is mainly installed in low-voltage DC distribution circuits to connect and disconnect the main circuit, and can also serve as an isolation device. Its symbol is "".
Rated current 800A~2500A;
Rated working voltage DC1000V and below;
Having a three pole string and a four pole string;
Drawer style and fixed style;
The product meets the following standards:
IEC60947-1 and GB14048.1 General Principles for Low Voltage Switchgear and Control Equipment
IEC60947-2 and GB14048.2 Low voltage switchgear and control equipment Circuit breakers
The product has obtained the national mandatory product certification CCC mark
2. Normal working conditions and installation conditions
The ambient air temperature is between -5 ℃ and+40 ℃, and the average value over 24 hours does not exceed+35 ℃;
The altitude of the installation site shall not exceed 2000m;
The relative humidity of the air at the installation site shall not exceed 50% at a maximum temperature of+40 ℃; At lower temperatures, there can be higher relative humidity, with the monthly average lowest temperature of the wettest month not exceeding+25 ℃, and the monthly average maximum relative humidity of that month not exceeding 90%, taking into account condensation on the surface of the product due to temperature changes;
The pollution level is level 3;
The installation category of the main circuit is IV, and the installation category of the other auxiliary circuits and control circuits is III;
The CW3DC DC universal circuit breaker should be installed according to the instructions in the user manual. Its vertical inclination does not exceed 5 °.
| Model number |
CW3DC-2500 |
| Shell level rated current Inm(A) |
two thousand and five hundred |
| Rated current In(A) |
800, 1000, 1250, 1600, 2000, 2500 |
| Rated working voltage Ue(V) |
DC 500/750 |
DC 750/1000 |
| Rated insulation voltage Ui(V) |
one thousand two hundred and fifty |
| Rated impulse withstand voltage Uimp(kV) |
twelve |
| Number of series poles |
Three pole string |
Quadrupole string |
| Rated ultimate short-circuit breaking capacity Icu (kA) |
forty |
| Rated operating short-circuit breaking capacity Ics (kA) |
forty |
| Rated short-circuit making capacity Icm (kA) |
100%Icu |
| Rated short-time withstand current Icw (kA)/1s |
forty |
| Usage category |
B |
| Opening time (without additional delay) (ms) |
30~40 |
| Closing time (ms) |
Maximum 70 |
| Electrical lifespan (times) |
seven thousand |
| Mechanical lifespan (times) |
maintenance-free |
twelve thousand and five hundred |
| There is maintenance |
twenty-five thousand |
Overall dimensions (mm) |
|
W |
H |
L |
| drawer-type |
Horizontal connection (rear) |
Three pole string |
three hundred and forty-seven |
four hundred and thirty-eight |
three hundred and ninety-five |
| Quadrupole string |
four hundred and forty-two |
four hundred and thirty-eight |
three hundred and ninety-five |
| Vertical connection (rear) |
Three pole string |
three hundred and forty-seven |
four hundred and thirty-eight |
three hundred and ninety-five |
| Quadrupole string |
four hundred and forty-two |
four hundred and thirty-eight |
three hundred and ninety-five |
| fixed type |
Horizontal connection (rear) |
Three pole string |
three hundred and sixty-two |
three hundred and ninety-five |
two hundred and ninety |
| Quadrupole string |
four hundred and fifty-seven |
three hundred and ninety-five |
two hundred and ninety |
CW3DC DC universal circuit breaker