F96-SM synchronization tableDetailed product description:

Q/F96-SM meter is an S-meter that integrates synchronization indication and synchronous pulse transmission. At a certain moment before the frequency difference between the generator to be connected and the system is less than a set value and the phase difference is 0 degrees, the closing indicator light is allowed to light up and the main switch closing command is issued to achieve automatic synchronization between the generator to be connected and the system.
F96-SM Synchronization Table Technical Performance
When the system voltage changes within the range of plus or minus 10% of the rated voltage and the absolute frequency difference between the generator to be connected and the system is less than 2HZ, the S-meter can work normally,
Frequency difference blocking range: set within 0.05-0.5HZ
Closing instruction lead time: 50MS-500MS setting
Working voltage: The line voltage between the system and the generator to be connected is 100 * 50Hz
Power consumption: less than 3VA
Output contact load capacity: AC 380 * 5A (resistive load) or DC 24V * 10A (resistive load)
Environmental conditions: The ambient temperature is 0-55 degrees Celsius, the relative humidity is 95%, and there is room for vibration, oil mist, and salt spray during ship operation
Dual channel insulation temporary measuring instrument
1、 Function Introduction: (Digital Display Type) 1. Real time monitoring of insulation resistance of two ungrounded AC systems, while displaying 2 temporary insulation measurement values; 2. Can set insulation alarm values for the power grid; 3. When an alarm is triggered, the alarm light flashes; The internal relay is engaged and outputs a control signal to the outside, which can be connected to a 220V alarm bell or an intermediate relay simultaneously; 4. The insulation detection value is restored, the alarm light is turned off, and the relay stops outputting control signals; 2、 Main technical indicators: 1. Power supply voltage: AC220V, power consumption:<5W. 2. Input: AC power grid level 1 (AC: 440V, 380V, 220V, etc.)
3. Output: The normally open contact capacity of the relay is 3A (AC: 250V)
4. It can work reliably at any tilt angle and during ship swaying and vibration;
5. Protection level: IP22;
6. Under the most unfavorable insulation conditions between power grids, the output current of each measuring terminal of the instrument shall not exceed 0.12MA

Related Products: