1. Scope of application
C2000H100 miniature circuit breaker is used for overload and short-circuit protection of lines and electrical equipment, suitable for lighting and motor distribution systems. It is used for distribution or protection of motors in circuits with a rated ultimate short-circuit capacity not exceeding 10000A.
2. Main technical parameters
Rated current: 63-125A (at 40 ℃)
Rated voltage: 230/400V AC
Breaking capacity: compliant with IEC947-2 standard
|
Rated current (A) |
Polar number (P) |
Rated voltage (V) |
Breaking ability (A) |
|
63,80 100,125 |
one |
two hundred and thirty |
ten thousand |
|
2,3,4 |
four hundred |
ten thousand |
Note: 125A only has lighting protection type
Reliable contact indication
Quick closure
Release characteristics:
Type C: (7-10) In instantaneous release
D-type: (10-14) In instantaneous release
Mechanical lifespan: 20000 cycles (disconnect connect)
Surge resistant voltage: 6kV
Isolation performance: reliable
Moisture and heat resistance: Class 2 (relative humidity of 95% at a temperature of 55 ℃)
Wiring:
Using wire terminals with clamps, the fixed cable section can reach 50mm2
Auxiliary devices: can be equipped with various auxiliary devices, including C2000 accessories
Compliant with IEC947-2 (GB14048.2) standard