1. Scope of application
The SS-21A time relay (hereinafter referred to as the relay) is suitable for various relay protection and automatic control circuits, enabling the controlled components to obtain the required high-precision delay.
3. Model
|
model |
rated voltage |
Rated range |
Rated level difference |
Contact type |
|
SS-21A |
DC 220V |
0.01-0.99s |
0.01s |
1 instantaneous motion conversion 1 delayed conversion |
|
DC 110V |
0.1-9.9s |
0.1s |
|
DC 48V |
1-99s |
1s |
Operating voltage: not exceeding 70% of the rated voltage.
Return voltage: not less than 5% of the rated value.
Setting error: not greater than ± 1% maximum setting value+0.050so
Delay consistency: not greater than 0.2% maximum setting value+0.050s.
Power consumption: not exceeding 12W.
Contact capacity: In a DC inductive load circuit with a voltage not exceeding 250V, a current not exceeding 5A, and a time constant of 5 ± 0.75ms, the output contact of the product has a breaking capacity of 50W. Under the specified load conditions, the output contact of the product can reliably operate and return 5 × 104 times. The long-term allowable current for the output contact is 5A.
Dielectric strength: The conductive terminals of the product are connected together and can withstand an AC voltage of 2000V (effective value) 50Hz for 1 minute between exposed non charged metal parts or shells without insulation breakdown or flashover.
Attached Resistance Specification Table:
|
model |
rated voltage |
specification |
|
SS-21A |
DC 220V |
3.6kΩ |
|
DC 110V |
1.7kΩ |
|
DC 48V |
0.5kΩ |
3. Internal wiring

4. Appearance and opening size

SS-21A type time relay