1. Scope of application
SS-61、 The 62 type time relay is mainly used in various control and relay protection circuits to achieve the purpose of automatic delay conversion circuits.
2. Main technical parameters
Rated voltage: AC50Hz, 220V, 127V, 110V, 100V; DC 220V、 110V、48V、24V;
Delay setting range: 1-999s.
Delay range: 1 second.
Contact form: Two pair delay conversion.
Action value: SS-61 action voltage not exceeding 85% of rated voltage (AC action); SS-62 operates at a voltage not exceeding 70% of the rated voltage (DC operation).
Return value: The return voltage is not less than 5% of the rated voltage.
Setting error: 1-9s not exceeding ± 3%; 10-9999s is not greater than ± 1%.
Consistency of action delay: not greater than 1% of the set value.
Power consumption: SS-61 not exceeding 4VA; SS-62 not exceeding 6.6W.
Contact capacity: In a DC inductive load circuit with a voltage not exceeding 250V, a current not exceeding 5A, and a time constant of 5 ± 0.75ms, the output contact of the product has a breaking capacity of 50W. Under the specified load conditions, the output contact of the product can reliably operate and return 5 × 104 times. The long-term allowable current for the output contact is 5A.
Dielectric strength: The conductive terminals of the product are connected together and can withstand an AC voltage of 2000V (effective value) 50Hz for 1 minute between exposed non charged metal parts or shells without insulation breakdown or flashover.
|
Power supply voltage (V) |
External resistor specifications |
quantity |
terminal block |
|
two hundred and twenty |
RXYC-20-3.6kΩ |
two |
① Compared to ⑦② and ⑧ |
|
one hundred and ten |
RXYC-20-1.8kΩ |
two |
① Compared to ⑦② and ⑧ |
|
forty-eight |
RXY-20-820kΩ |
two |
① Compared to ⑦② and ⑧ |
|
twenty-four |
not accept |
|
3. Internal wiring

4.SS-61、 Appearance and opening size of 62 type time relay

SS-61、 62 type time relay