Main technical parameters
1. Relay starting value: The starting voltage of the voltage starting type shall not be less than 30% of the rated voltage, and shall not exceed 70% of the rated voltage; The starting current range of the current starting type is universal between 0.01 and 2A.
2. Power consumption:
a、 Start circuit:
The voltage starting type has a starting current of no more than 3W; the current starting type has a starting current of 2A and no more than 6W.
b、 Auxiliary power supply circuit (during operation):
At DC48V, not more than 1.5W; at DC110V, not more than 3W; at DC220V, not more than 5.5W.
3. Action time: no more than 15ms.