HomeYour location:Homelow-voltage electrical apparatusrelayPhase failure relay → APR-L Under reverse phase protection relay
Column tabs 
Product name: APR-L Under reverse phase protection relay
specification: APR-L Under reverse phase protection relay
  Zoom Zoom in on the image
Category: low-voltage electrical apparatus -- Phase failure relay
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


APR-L Under reverse phase protection relayDetailed product description:Column tabs
APR-L under reverse phase protection relay

Can confirm the phase sequence of the three-phase power supply to prevent motor reversal
Wiring according to the diagram can prevent the electromagnetic contactor from operating in case of phase loss
APR-L under reverse phase protection relay adopts voltage output mode independent of load current
Low voltage protection range 20%

model APR-L,APR-LVM
rated voltage AC(V):220,240,380,415,440,50/60Hz
Output contact 1C 10A
Indicator light action Power on indication

longevity

fate

Mechanics 5×10^6 times
Electrical 10^5 times
Setting error --
Return time 3 sec
power consumption 2VA
Environmental temperature for use -10℃~+55℃
Environmental humidity for use 45%~85%RH
weight Approx.130g


APR-L under reverse phase protection relay wiring diagram and timing diagram

APR-L under reverse phase protection relay wiring diagram

Appearance dimension diagram of APR-L under reverse phase protection relay

Installation dimensions of APR-L under reverse phase protection relay

APR-L under reverse phase protection relay

APR-L Under reverse phase protection relay