| Product name: | S-102.5 type porcelain cross arm insulator | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Porcelain insulator | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
S-102.5 porcelain cross arm insulator is used for insulation and supporting conductors in high-voltage overhead transmission and distribution lines. It can replace suspension insulators and pin insulators. The porcelain cross arm insulator is made of solid and non penetrable porcelain parts and metal accessories glued together, which has the advantages of good self-cleaning, simple maintenance, low line material consumption, low cost, and safe and reliable operation.
Model Description: S - High Voltage Line Ceramic Cross arm Insulator; The number after the model is the design sequence number; The fraction formula after a dash, with the numerator being the rated voltage (kV) and the denominator being the rated bending failure load (kV).
|
factory code name |
model | drawing number |
cable duct and mounting hole center distance L |
insulation distance lone |
cable duct size |
installation dimensions |
Stable hole diameter dtwo±0.5 |
mounting hole And stability Center distance of holes a±1 |
The smallest public Called crawling electricity distance |
heavy quantity kg | ||
| ltwo |
R |
Hole diameter done ±0.5 |
height h ≤ | |||||||||
| fourteen thousand one hundred and seven | S-10/2.5 | one | three hundred and ninety | three hundred and fifteen | twenty-two | eleven | eighteen | fourteen | six point five | forty | three hundred and twenty | five |
| fourteen thousand one hundred and fifteen | S-35/5.0 | two | five hundred and eighty | four hundred and ninety | twenty-eight | fourteen | twenty-two | one hundred and forty | eleven | forty | seven hundred | twelve point two |
|
factory code name |
model | drawing number |
Power frequency wet withstand voltage kV r.m.s |
Lightning full wave impulse withstand voltage kV peak |
Rated bending failure load kN |
| fourteen thousand one hundred and seven | S-10/2.5 | one | forty-five | one hundred and sixty-five | two point five |
| fourteen thousand one hundred and fifteen | S-35/5.0 | two | eighty-five | two hundred and fifty | five |