| Product name: | C2000NLE-32 Miniature residual current circuit breaker | ||||||
| specification: | ![]() |
||||||
| Category: | low-voltage electrical apparatus -- Residual Current Circuit Breaker | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
Rated current of shell level (A) |
polar number |
Rated current (A) |
Rated voltage (V) |
Short circuit capability during operation |
Type of overcurrent instantaneous release device | |
|
Short circuit capability during operation (A) |
¢COS | |||||
|
Wire cross-sectional area S (mm)two) |
1P+N |
6. 10, 15, 20, 25, 32 |
two hundred and thirty |
four thousand and five hundred |
zero point eight zero |
Type C |
|
In(A) |
In(A) |
The residual current (I) is equal to the following | |||
|
In |
2In |
5In |
500A | ||
|
6-32 |
zero point zero three |
0.1S |
0.08S |
0.04S |
0.04S |
|
serial number |
Rated current of release device In |
Initial state |
test current |
specified time |
expected result |
Test environment temperature |
remark |
|
a |
≤32A |
cold state |
1.13In |
t≥1h |
Do not release |
30°C~35°C |
|
|
b |
Immediately following item a After the experiment, proceed |
1.45In |
t < 1h |
trip |
The current steadily rises to the specified value within 5 seconds | ||
|
c |
cold state |
2.55In |
1s |
trip |
|||
|
d |
cold state |
5In |
t≥0.1s |
Do not release |
Connect the current by closing the auxiliary switch | ||
|
e |
cold state |
10In |
t < 0.1s |
trip |
|
Rated current In (A) |
In≤6 |
6 < In≤13 |
13 < In≤20 |
20 < In≤25 |
25 < In≤32 |
|
Wire cross-sectional area S (mm)two) |
one |
one point five |
two point five |
four |
six |
3. Structural characteristics
The product has a small volume, compact structure, and a better price ratio than similar products.
The product shell and some functional components are made of high flame retardant, high temperature resistant, and impact resistant plastic.
The product is directly installed with a neutral wire to avoid potential electric shock hazards caused by incorrect neutral wire wiring.
The product adopts the latest circuit design and high-performance components, which have strong resistance to surge current and overvoltage, without causing misoperation.
The product adopts guide rail installation, which is convenient and time-saving.