HomeYour location:Homelow-voltage electrical apparatuschangeover switchCAM switch → LWX1,LW1B,LWX2 series universal transfer switch
Column tabs 
Product name: LWX1,LW1B,LWX2 series universal transfer switch
specification: LWX1,LW1B,LWX2 series universal transfer switch
  Zoom Zoom in on the image
Category: low-voltage electrical apparatus -- CAM switch
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


LWX1,LW1B,LWX2 series universal transfer switchDetailed product description:Column tabs
purpose

LWX1, LW1B, and LWX2 universal transfer switches are suitable for electrical equipment, used for remote control of various distribution equipment, and can also be used for conversion of various instruments, servos, and micro motors.

Product model and its meaning
LWX1, LW1B, LWX2 series universal transfer switch model description
Positioning type code: 8 represents 45o positioning
Panel form: F-shaped, Y-shaped

LWX1, LW1B, LWX2 series universal transfer switch classification

1. Classified by structural form
Handle non removable positioning type, handle removable positioning type (indicated by "H")
Self replication (represented by "W"), localization self replication (represented by "Z")

Divided by operating angle
There are 30 ° and 90 °

Main technical parameters of LWX1, LW1B, LWX2 series universal transfer switches
Model
LWX1
LWX1B
LWX2
Agreed heating current lth
A
five
five
five
Rated working voltage Ue
V
two hundred and twenty
two hundred and twenty
two hundred and twenty
Rated working current le
AC-15
A
zero point five
zero point five
zero point five
AC-13
A
zero point two four
zero point two four
zero point two four


Mechanical and electrical lifespan
Mechanical lifespan: 0.1 × 106 times, self replication is 0.05 × 106 times, operating frequency is 120 times/hour.
Electric lifespan: 0.03 × 106 at AC-15, operating frequency of 120 times/hour.
At DC-13, the frequency is 0.01 × 106 times and the operating frequency is 120 times/hour

Overall dimensions

LWX1 switch
LWX1, LW1B, LWX2 series universal transfer switch with external dimensions of 1

LWX1B switch
LWX1, LW1B, LWX2 series universal transfer switch with external dimensions of 2

LWX2 switch
LWX1, LW1B, LWX2 series universal transfer switch with external dimensions of 3

Note: n is the number of contact system sections

installation dimensions
LWX1, LW1B, LWX2 series universal conversion switch opening size

LWX1, LW1B, LWX2 series universal transfer switch

LWX1,LW1B,LWX2 series universal transfer switch