| model |
Rated current (A) |
Range of action current setting (A) |
Grade difference (A) |
Inverse time delay time under 10 times action current (s) |
Output contact form |
Speed multiplier |
return coefficient |
AC circuit power consumption (VA) |
Contact breaking capacity |
| AC Circuit (VA) |
DC circuit (W) |
| SL-61/ |
two |
1-2.5 |
zero point one |
0.5-4 |
A pair of dynamic contact points |
2 - 10 |
≥0.9 |
≤6 |
two hundred and fifty |
thirty |
| five |
2-5 |
| ten |
4-10 |
| SL-62/ |
two |
1-2.5 |
1-1.6 |
| five |
2-5 |
| ten |
4-10 |
| SL-63/ |
two |
1-2.5 |
0.5-4 |
A pair of dynamic contact points and a pair of conversion contact points |
| five |
2-5 |
| ten |
4-10 |
| SL-64/ |
two |
1-2.5 |
1-1.6 |
| five |
2-5 |
| ten |
4-10 |


SL-61, SL-62, SL-63, SL-64 series static overcurrent relays