| Product name: | LQGZ-0.66 Current Transformer | ||||||
| specification: | ![]() |
||||||
| Category: | low-voltage electrical apparatus -- Low voltage current transformer | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
The LQGZ-0.66 current transformer is an indoor fully epoxy resin cast type. Most of the products are wound with a ring-shaped amorphous iron core, and the secondary coil is evenly wound around the ring-shaped iron core. The primary coil is made of high-quality copper tape or glass fiber wrapped wire that runs through the secondary coil. The product accuracy can reach 0.2S level. And it adopts fully enclosed casting insulation, which has good moisture-proof effect. Suitable for measuring current, electrical energy, and relay protection in AC lines with a frequency of 50Hz (or 60Hz) and a voltage of 0.66kV or below. The product complies with the GB1028-1997 standard for current transformers.
2、 Environmental conditions for use
1. Altitude not exceeding 1000m
2. Environmental temperature: -5 ℃~40 ℃;
3. The relative humidity of the air is below 85% (at 20 ℃);
4. There is no pollution, corrosive or explosive medium in the atmosphere that seriously affects the insulation of the transformer.
3、 Technical parameters of LQGZ-0.66 current transformer
1. Rated voltage: 0.66kV
2. Rated frequency: 50Hz (60Hz)
3. Rated primary current: 5 A、10A、15A、20A、30A、40A、50A、60A、75A、100A、150A、200A、300A、400A、500A、600A、750A、800A、1000A
4. Rated secondary current: 5A
5. Accuracy levels: 0.5, 0.5S, 0.2, 0.2S
6. Rated capacity: 5VA, 10VA
|
Accuracy level and error value | ||||||||||
|
accuracy level
|
Current error (±%) at the following rated currents (%) |
Phase difference, at the following rated current (%) ± (min)
| ||||||||
|
five |
twenty |
one hundred |
one hundred and twenty |
five |
twenty |
one hundred |
one hundred and twenty | |||
|
zero point two |
zero point seven |
zero point three |
zero point one eight |
zero point one eight |
twenty-eight |
thirteen |
eight |
eight | ||
|
zero point five |
one point two |
zero point seven two |
zero point four five |
zero point four five |
eighty-five |
forty |
twenty-seven |
twenty-seven | ||
|
Error values of special purpose current transformers | ||||||||||
|
accuracy level
|
Current error (±%) at the following rated currents (%)
|
Phase difference, at the following rated current (%) ± (min) | ||||||||
|
one |
five |
twenty |
one hundred |
one hundred and twenty |
one |
five |
twenty |
one hundred |
one hundred and twenty | |
|
zero point seven |
zero point three |
zero point one eight |
zero point one eight |
zero point one eight |
twenty-seven |
thirteen |
eight |
eight |
eight | |
|
one point two |
zero point seven |
zero point four five |
zero point four five |
zero point four five |
eighty-five |
forty-five |
twenty-eight |
twenty-eight |
twenty-eight | |