HomeYour location:Homelow-voltage electrical apparatuslow-voltage contactorDC contactor → ZJW50A DC contactor
Column tabs 
Product name: ZJW50A DC contactor
specification: ZJW50A DC contactor
  Zoom Zoom in on the image
Category: low-voltage electrical apparatus -- DC contactor
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


ZJW50A DC contactorDetailed product description:Column tabs
purpose
The ZJW50A series DC contactor is suitable for battery or rectifier power supply; Used to operate power switches for traction, pump motors, and other electric vehicles. It is widely used in electronic control systems such as communication power supplies and uninterruptible power supplies.

Brief Technical Parameters

Rated current of main contact Resistive load τ=1ms, 50A
dielectric strength 50Hz 1000V AC 1min
Action Time Cold suction time: ≯ 30ms, release: ≯ 30ms
Action characteristics Cold suction voltage: ≯ 66%, cold release voltage: ≯ 30%, ≮ 5%
mechanical life 1 million times
Electrical lifespan Resistive load (τ=1ms): 50000 cycles, inductive load (DC-5): 60% le for resistive load, 10000 cycles
The coil consumes less than 15 watts of power,
Maximum current of coil (A)
Rated voltage of coil and contact (V)
twelve twenty-four thirty thirty-six forty forty-eight sixty seventy-two eighty
zero point nine eight zero point five eight zero point four five zero point three five zero point three two zero point two eight zero point two five zero point two zero point one eight
Note: 1. The coil parameters can be changed according to user requirements. 2. Install a magnetic blow out arc device when the coil voltage is above 48V


Terms of Use
1. Environmental temperature: -25~+40 ℃;  
2. Altitude: 0-2000 meters;  
3. Maximum relative humidity at 25 ℃: 90%;  
4. Vibration at fixed location: 10~50Hz, 10m/s2;  
5. Impact: 30m/s2
6. Installation direction: Any
7. Power supply voltage fluctuation range: 0.7-1. 1Ue
8. Work schedule: 8H long hours

Appearance and installation diagram of ZJW50A DC contactor

Installation dimensions of ZJW50A DC contactor

Circuit schematic diagram

ZJW50A DC contactor wiring diagram

Product model meaning

Model Description of ZJW50A DC Contactor

ZJW50A DC contactor
Product Category
All product information on this website is translated by Baidu machine translation, which may not be completely accurate and is only for reference