DDS237-1 single-phase electronic energy meterDetailed product description:Column tabs
Specification and main parameters of DDS237-1 single-phase electronic energy meter

Specification and model: DDS237-1
Accuracy level: 1.0 level
Reference voltage (V): 220 230 240
Reference current (A)
2.5 (10), 5 (20), 10 (40), 15 (60), 20 (80)
Meter constant (imp/kWh)
3200, 1600, 800
basic error
load current
power factor
Basic error (%)
0.05Ib ≤ I ≤ 0.1Ib
one
± 1.5
0.1Ib ≤ I ≤ Imax
one
± 1.0
0.1Ib ≤ I ≤ 0.2Ib
0.5L 0.8C
± 1.5
0.2Ib ≤ I ≤ Imax
0.5L 0.8C
± 1.0
start
Under the conditions of reference voltage, reference frequency, and power factor of 1, the meter can start and continuously record when the load current is 0.4% Ib.
Stealth
When a reference voltage of 115% is applied, the circuit is disconnected and no more than one electrical energy pulse is output.
Electrical parameters
Normal operating voltage: 0.9-1.1 reference voltage
Maximum operating voltage: 0.6~1.25 reference voltage
Insulation voltage: ≥ 2000VAC
Power consumption:<1W, 5VA