DHC-X series phase loss and phase sequence protection relayDetailed product description:Column tabs
The DHC X series phase loss and phase sequence protection relay is used in conjunction with an AC contactor for the phase mismatch of three-phase power supplies in AC 380V Lack of phase Motor protection against phase voltage imbalance and overvoltage/undervoltage

Adopting voltage sampling method It is independent of the power of the motor
Series products There are multiple different functions to choose from To achieve different protection purposes
Installation method of guide rail International standard installation dimensions
SMT process
Reliable performance Beautiful appearance High performance price ratio

function
DHC1X
Phase sequence protector (RSTC)
DHC2X
3-phase 3-wire phase sequence protector for phase loss
DHC2X-T
3-phase 3-wire phase sequence protector for phase loss
DHC2X-N
3-phase 4-wire phase sequence protector with missing phase
DHC1X-T
Phase voltage phase sequence protector (RSTB)
Outline drawing 1 of DHC-X series phase loss and phase sequence protection relay Outline drawing 2 of DHC-X series phase loss and phase sequence protection relay Outline drawing 3 of DHC-X series phase loss and phase sequence protection relay Outline drawing 4 of DHC-X series phase loss and phase sequence protection relay Outline drawing 5 of DHC-X series phase loss and phase sequence protection relay
Phase sequence error
Immediate action
Immediate action
Immediate action
Immediate action
Immediate action
Failed to start due to phase loss
Phase loss and disconnection
10% overvoltage/undervoltage detection
√ Voltage fine-tuning is available
3 phases and 3 wires
3 phases and 4 wires
Sensitivity adjustment
10% fixed
5%~20%
5%~20%
action delay
0.1S
3S
1-10S
0.2S
1-10S
Applicable to
Phase sequence error protection. It can also be used for three-phase phase loss protection of motors that start frequently
It is a simplified version of DHC2X-T's features
Phase sequence error protection and phase loss protection for 3-phase 3-wire motors
Phase sequence error protection and phase loss protection for 3-phase 4-wire motors
Three phase imbalance, undervoltage, overvoltage, and undervoltage and overvoltage protection for each phase. And phase loss protection