LZZBJ8-35W1B current transformer is suitable for precise electrical measurement and relay protection in power systems with an altitude of 1000m and below, a rated frequency of 50Hz, and a maximum operating voltage of 40.5kV and below.
Environmental temperature: The normal type is+40 ℃~-15 ℃; The plateau type ranges from+25 ℃ to -15 ℃.
Environmental humidity: The daily average relative humidity should not exceed 95%, and the monthly average should not exceed 90%; The daily average saturated vapor pressure shall not exceed 2.2 × 10-3MPa, and the monthly average shall not exceed 1.8 × 10-3MPa.
Product type: Indoor.
Atmospheric conditions: There is no pollution or explosive medium in the installation site that seriously affects the insulation of the transformer.
The installation site has no severe vibrations or bumps.
Open circuit is not allowed during product operation, otherwise there is a high voltage hazard.
The temperature during transportation and storage ranges from+40 ℃ to -15 ℃.
When using the product, the equipotential lead wire should be reliably connected to the high-voltage bus.
Technical parameters of LZZBJ8-35W1B current transformer
Product execution standard: GB1208-1997 "Current Transformers".
Rated insulation level: 40.5/95/185kV.
Rated secondary current: 5A and 1A.
Instrument security factor: 0.2S level FS ≤ 5; Level 0.2 and 0.5 FS ≤ 10.
Insulation and heat resistance grade: Grade E.
Secondary structure: two coils, three coils, four coils.
The rated secondary lower limit load is 25% of the rated secondary load.
The rated primary current value, rated secondary load, accurate limit coefficient, rated short-time current value, level combination, and weight are listed in the following table. Please consult with the manufacturer for special specification products.
Rated primary current (A) | Rated secondary load (VA) COS ∧=0.8 | 5P, 10P accurate limit coefficient | 1S short Time heat current (KA) | rated Dynamic stability Constant current (KA) |
0.2S | zero point two | zero point five | 5P、10P | 5P | 10P |
1A | 5A | 1A | 5A | 1A | 5A | 1A | 5A | 1A | 5A | 1A | 5A |
twenty | | ten | ten | ten | ten | fifteen | fifteen | fifteen | fifteen | fifteen The twenty | fifteen | fifteen The twenty | 200I1n /1S | 500I1n |
thirty |
forty |
fifty |
seventy-five |
one hundred | |
one hundred and fifty | 31.5KA /1S | eighty |
two hundred | |
three hundred | 31.5kA/2S | eighty |
four hundred | 31.5kA /4S | one hundred and thirty |
five hundred |
six hundred | fifteen | ten | fifteen | ten | thirty | 15\20 |
seven hundred and fifty | twenty | twenty | twenty | twenty |
one thousand | twenty | twenty |
one thousand two hundred and fifty | thirty | 20. 30 |
one thousand and five hundred | thirty | thirty | forty | thirty | 40kA /4S | one hundred and thirty |
LZZBJ8-35W1B type current transformer