Product Features:
Using a unique formula of highly elastic silicone rubber as insulation material, silicone rubber has many advantages as external insulation:
1. The most resistant to suspended chemical pollutants, not easy to stick to dust, resistant to high temperatures, acid and alkali corrosion.
2. Natural anti ultraviolet and anti-aging ability.
3. Good insulation performance, difficult to generate conductive carbide channels, excellent anti creepage performance, and insulation regeneration ability.
4. It is a hydrophobic substance that can maintain high surface resistance.
5. Has hydrophobic recovery function.
Cold shrink installation method, easy to install:
Peel off the cable and fix the cold shrink end according to the specified size, extract the support strip and install it.
Product Usage
Used for connecting indoor or outdoor low-voltage cables (terminals or intermediate joints), as well as for the outgoing lines of motors below 6kV. One model is suitable for multiple wire diameters. And ensure excellent waterproofing, insulation, and mechanical strength. Due to the elongation of the insulation tube, it is particularly suitable for connecting cables and distribution cabinets
Product selection table:
Product Name:
1kV cold shrink terminal, intermediate joint, (single core, three core, four (3+1) core, five (3+2, 4+1) core)
Product Model:
GCB-DT (Terminal)
Product Features:
Using a unique formula of highly elastic silicone rubber as insulation material, silicone rubber has many advantages as external insulation:
1. The most resistant to suspended chemical pollutants, not easy to stick to dust, resistant to high temperatures, acid and alkali corrosion.
2. Natural anti ultraviolet and anti-aging ability.
3. Good insulation performance, difficult to generate conductive carbide channels, excellent anti creepage performance, and insulation regeneration ability.
4. It is a hydrophobic substance that can maintain high surface resistance.
5. Has hydrophobic recovery function.
Cold shrink installation method, easy to install:
Peel off the cable and fix the cold shrink end according to the specified size, extract the support strip and install it.
Product Usage
Used for connecting indoor or outdoor low-voltage cables (terminals or intermediate joints), as well as for the outgoing lines of motors below 6kV. One model is suitable for multiple wire diameters. And ensure excellent waterproofing, insulation, and mechanical strength. Due to the elongation of the insulation tube, it is particularly suitable for connecting cables and distribution cabinets
Product selection table:
|
Product Name |
Product Model |
voltage level |
Application cable cross-section (mm)two) |
|
Cold shrink terminal |
GCB-DT0 |
1kV
|
25-35 |
|
GCB-DT1 |
50-70 |
|
GCB-DT2 |
95-120 |
|
GCB-DT3 |
150-240 |
|
GCB-DT4 |
three hundred |
Note: According to customer needs, the maximum cross-sectional area of the applied cable can reach 800 mm2
Product performance
|
Serial number |
name |
Cold shrink cable terminal |
|
one |
model |
GCB-DT |
|
two |
Nominal voltage (kV): |
0.6/1 |
|
three |
Maximum allowable continuous operating voltage (kV): |
one point two |
|
four |
Normal operating temperature (℃) |
ninety |
|
five |
Temperature during short circuit (℃) |
two hundred and fifty |
|
six |
transmission capacity |
Consistent with the cable |
|
seven |
Short circuit capacity |
Consistent with the cable |
|
eight |
Creepage distance ratio |
Greater than 3.1cm/kV |
|
nine |
Implement standards for connecting with devices |
GB/T 14315 |
|
ten |
Height (length) |
According to customer requirements |
|
eleven |
The short-circuit current allowed to pass through the grounding part |
Not less than the selected cable |
|
twelve |
Weight (kg/piece) |
1.5kg/set |