XCR8 (3RU) thermal overload relay
Main technical parameters
|
Order Number |
Suitable for AC motor with P) kw |
Set current range A |
Fuse specification A |
| S00 specification, with coil and auxiliary contact lead out terminal XCR8-12 |
3RU11 16-0AB0 |
zero point zero four |
0.11-0.16 |
zero point five |
| 3RU11 16-0BB0 |
zero point zero six |
0.14-0.2 |
one |
| 3RU11 16-0CB0 |
zero point zero six |
0.18-0.25 |
one |
| 3RU11 16-0DB0 |
zero point zero nine |
0.22-0.32 |
one point six |
| 3RU11 16-0EB0 |
zero point zero nine |
0.28-0.4 |
two |
| 3RU11 16-0FB0 |
zero point one two |
0.35-0.5 |
two |
| 3RU11 16-0GB0 |
zero point one eight |
0.45-0.63 |
two |
| 3RU11 16-0HB0 |
zero point one eight |
0.55-0.8 |
four |
| 3RU11 16-0JB0 |
zero point two five |
0.7-1 |
four |
| 3RU11 16-0KB0 |
zero point three seven |
0.9-1.25 |
four |
| 3RU11 16-1AB0 |
zero point five five |
1.1-1.6 |
six |
| 3RU11 16-1BB0 |
zero point seven five |
1.4-2 |
six |
| 3RU11 16-1CB0 |
zero point seven five |
1.8-2.5 |
ten |
| 3RU11 16-1DB0 |
one point one |
2.2-3.2 |
ten |
| 3RU11 16-1EB0 |
one point five |
2.8-4 |
sixteen |
| 3RU11 16-1FB0 |
one point five |
3.5-5 |
twenty |
| 3RU11 16-1GB0 |
two point two |
4.5-6.3 |
twenty |
| 1RU11 16-1HB0 |
three |
5.5-8 |
twenty-five |
| 1RU11 16-1JB0 |
four |
7-10 |
thirty-five |
| 1RU11 16-1KB0 |
five point five |
9-12 |
thirty-five |
| S0 specification XCR8-25 |
3RU11 26-1CB0 |
zero point seven five |
1.8-2.5 |
ten |
| 3RU11 26-1DB0 |
one point one |
2.2-3.2 |
ten |
| 3RU11 26-1EB0 |
one point five |
2.8-4 |
sixteen |
| 3RU11 26-1FB0 |
one point five |
3.5-5 |
twenty |
| 3RU11 26-1GB0 |
two point two |
4.5-6.3 |
twenty |
| 3RU11 26-1HB0 |
three |
5.5-8 |
twenty-five |
| 3RU11 26-1JB0 |
four |
7-10 |
thirty-five |
| 3RU11 26-1KB0 |
five point five |
9-12.5 |
thirty-five |
| 3RU11 26-4AB0 |
seven point five |
11-16 |
forty |
| 3RU11 26-4BB0 |
seven point five |
14-20 |
fifty |
| 3RU11 26-4CB0 |
eleven |
17-22 |
sixty-three |
| 3RU11 26-4DB0 |
eleven |
20-25 |
sixty-three |
| S2 specification XCR8-50 |
3RU11 36-1HB0 |
three |
5.5-8 |
twenty-five |
| 3RU11 36-1JB0 |
four |
7-10 |
three point five |
| 3RU11 36-1KB0 |
five point five |
9-12.5 |
thirty-five |
| 3RU11 36-4AB0 |
seven point five |
11-16 |
forty |
| 3RU11 36-4BB0 |
seven point five |
14-20 |
fifty |
| 3RU11 36-4DB0 |
eleven |
18-25 |
sixty-three |
| 3RU11 36-4EB0 |
fifteen |
22-32 |
eighty |
| 3RU11 36-4FB0 |
eighteen point five |
28-40 |
eighty |
| 3RU11 36-4GB0 |
twenty-two |
36-45 |
one hundred |
| 3RU11 36-4HB0 |
twenty-two |
40-50 |
one hundred |
| S2 specification XCR8-100 |
3RU11 46-4DB0 |
three |
5.5-8 |
twenty-five |
| 3RU11 46-4EB0 |
four |
7-10 |
three point five |
| 3RU11 46-4FB0 |
five point five |
9-12.5 |
thirty-five |
| 3RU11 46-4HB0 |
seven point five |
11-16 |
forty |
| 3RU11 46-4JB0 |
seven point five |
14-20 |
fifty |
| 3RU11 46-4KB0 |
eleven |
18-25 |
sixty-three |
| 3RU11 46-4LB0 |
fifteen |
22-32 |
eighty |
| 3RU11 46-4MB0 |
eighteen point five |
28-40 |
eighty |
1) Pay attention to the maximum rated working current of the product;
2) Under the conditions of 50Hz and 400V communication, the reference value of a four pole standard motor is determined by the actual starting data and rated data of the protected motor for product selection;
3) The largest fuse specification, for overload relays and coordination category 2
XCR8 (3RU) thermal overload relay appearance and installation dimensions

XCR8 (3RU) thermal overload relay