HomeYour location:Homespare parts and accessoriesvacuum interrupterGlass arc extinguishing chamber → BD-12/2000-31.5 Vacuum arc extinguishing chamber
Column tabs 
Product name: BD-12/2000-31.5 Vacuum arc extinguishing chamber
specification: BD-12/2000-31.5 Vacuum arc extinguishing chamber
  Zoom Zoom in on the image
Category: spare parts and accessories -- Glass arc extinguishing chamber
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


BD-12/2000-31.5 Vacuum arc extinguishing chamberDetailed product description:Column tabs
Overview:

The BD-12/2000-31.5 vacuum arc extinguishing chamber is a miniaturized product that uses copper chromium contact material, cup-shaped longitudinal magnetic field structure, glass insulation surgery, and a middle sealed fixed shielding cylinder. The product has the characteristics of small size, large breaking capacity, and high pressure resistance. Paired with corresponding indoor and outdoor vacuum circuit breakers, it can be widely used in places where circuits are frequently operated in industrial sectors such as power, machinery, chemical, metallurgical, and mining.

Main technical parameters of BD-12/2000-31.5 vacuum arc extinguishing chamber

parameter item unit parameter
rated voltage kV twelve
rated current A two thousand
rated frequency Hz fifty
Short term (1-minute) power frequency withstand voltage kV forty-two
Lightning impulse withstand voltage kV seventy-five
Rated short-circuit breaking current kA thirty-one point five
Rated peak withstand current kA eighty
Rated short-circuit closing current kA eighty
Rated short-time withstand current kA thirty-one point five
Rated short-circuit duration S four
Rated breaking current of a single capacitor bank A six hundred and thirty
Rated back-to-back capacitor bank breaking current A four hundred
Rated operating sequence Fen-0.3 (0.5) S-HeFen-180S-HeFen
Rated short-circuit breaking current breaking times time thirty
mechanical life time ten thousand
Contact self closing force N 200±60
Contact reaction force N 300±60
Circuit resistance at lower limit of rated contact pressure ≤25
Thickness of allowable wear of contacts mm three
Gas pressure inside the vacuum arc extinguishing chamber Pa ≤1×10
Quality of the sports section kg two point one
Quality of vacuum arc extinguishing chamber kg five point three

Outline dimensions of vacuum arc extinguishing chamber BD-12/2000-31.5

BD-12/2000-31.5 Vacuum arc extinguishing chamber
Product Category
All product information on this website is translated by Baidu machine translation, which may not be completely accurate and is only for reference