Overview:
The BD-12/2000-31.5 vacuum arc extinguishing chamber is a miniaturized product that uses copper chromium contact material, cup-shaped longitudinal magnetic field structure, glass insulation surgery, and a middle sealed fixed shielding cylinder. The product has the characteristics of small size, large breaking capacity, and high pressure resistance. Paired with corresponding indoor and outdoor vacuum circuit breakers, it can be widely used in places where circuits are frequently operated in industrial sectors such as power, machinery, chemical, metallurgical, and mining.
Main technical parameters of BD-12/2000-31.5 vacuum arc extinguishing chamber
| parameter item |
unit |
parameter |
| rated voltage |
kV |
twelve |
| rated current |
A |
two thousand |
| rated frequency |
Hz |
fifty |
| Short term (1-minute) power frequency withstand voltage |
kV |
forty-two |
| Lightning impulse withstand voltage |
kV |
seventy-five |
| Rated short-circuit breaking current |
kA |
thirty-one point five |
| Rated peak withstand current |
kA |
eighty |
| Rated short-circuit closing current |
kA |
eighty |
| Rated short-time withstand current |
kA |
thirty-one point five |
| Rated short-circuit duration |
S |
four |
| Rated breaking current of a single capacitor bank |
A |
six hundred and thirty |
| Rated back-to-back capacitor bank breaking current |
A |
four hundred |
| Rated operating sequence |
|
Fen-0.3 (0.5) S-HeFen-180S-HeFen |
| Rated short-circuit breaking current breaking times |
time |
thirty |
| mechanical life |
time |
ten thousand |
| Contact self closing force |
N |
200±60 |
| Contact reaction force |
N |
300±60 |
| Circuit resistance at lower limit of rated contact pressure |
uΩ |
≤25 |
| Thickness of allowable wear of contacts |
mm |
three |
| Gas pressure inside the vacuum arc extinguishing chamber |
Pa |
≤1×10 |
| Quality of the sports section |
kg |
two point one |
| Quality of vacuum arc extinguishing chamber |
kg |
five point three |