Product Overview:
TD-12/2000-31.5 vacuum arc extinguishing chamber is a miniaturized product, using copper chromium contact material, cup-shaped longitudinal magnetic field structure, and large creepage distance ceramic insulation shell. The product has the characteristics of small size, large breaking capacity, and high insulation level. Matched with corresponding vacuum circuit breakers or vacuum distribution devices, it is particularly suitable for places where circuits are frequently operated in all working conditions of departments such as power, machinery, chemical, metallurgical, mining, etc.
TD-12/2000-31.5 Main technical parameters of vacuum arc extinguishing chamber
| parameter item |
unit |
parameter |
| rated voltage |
kV |
twelve |
| rated current |
A |
two thousand |
| rated frequency |
Hz |
fifty |
| Short term (1-minute) power frequency withstand voltage |
kV |
forty-two |
| Lightning impulse withstand voltage |
kV |
seventy-five |
| Rated short-circuit breaking current |
kA |
thirty-one point five |
| Rated peak withstand current |
kA |
eighty |
| Rated short-circuit closing current |
kA |
eighty |
| Rated short-time withstand current |
kA |
thirty-one point five |
| Rated short-circuit duration |
S |
four |
| Rated breaking current of a single capacitor bank |
A |
six hundred and thirty |
| Rated back-to-back capacitor bank breaking current |
A |
four hundred |
| Rated operating sequence |
|
Fen-0.3 (0.5) S-HeFen-180S-HeFen |
| Rated short-circuit breaking current breaking times |
time |
thirty |
| mechanical life |
time |
ten thousand |
| Contact self closing force |
N |
210±30 |
| Contact reaction force |
N |
300±70 |
| Circuit resistance at lower limit of rated contact pressure |
uΩ |
≤15 |
| Thickness of allowable wear of contacts |
mm |
three |
| Gas pressure inside the vacuum arc extinguishing chamber |
Pa |
≤1×10 |
| Quality of the sports section |
kg |
two point two |
| Quality of vacuum arc extinguishing chamber |
kg |
six point six |
The mechanism characteristics and parameters of the vacuum switch equipment matched with the product
| parameter item |
unit |
parameter |
| contact gap |
mm |
11±1 |
| Average opening speed |
m/s |
1.1±0.2 |
| Average closing speed |
m/s |
0.6±0.2 |
| Rated contact pressure |
N |
3100±200 |
| Contact closing bounce time |
ms |
≤2 |
| Non synchronous closing and opening of contacts |
ms |
≤1 |
| Rebound amplitude of the opening contact |
mm |
≤2 |