Product Overview:
TD-40.5/1600-31.5 vacuum arc extinguishing chamber adopts copper chromium contact material, cup-shaped longitudinal magnetic field structure, stainless steel corrugated tube, ceramic shell and exposed shielding tube. The product has the characteristics of large breaking capacity, good insulation performance, and long mechanical life. Paired with corresponding vacuum circuit breakers, it can be widely used in power systems as a control and protection device for circuits, especially suitable for places with frequent operation.
Main technical parameters of vacuum arc extinguishing chamber
| parameter item |
unit |
parameter |
| rated voltage |
kV0 |
forty point five |
| rated current |
A |
one thousand and six hundred |
| rated frequency |
Hz |
fifty |
| Short term (1-minute) power frequency withstand voltage |
kV |
ninety-five |
| Lightning impulse withstand voltage |
kV |
one hundred and eighty-five |
| Rated short-circuit breaking current |
kA |
thirty-one point five |
| Rated peak withstand current |
kA |
eighty |
| Rated short-circuit closing current |
kA |
eighty |
| Rated short-time withstand current |
kA |
thirty-one point five |
| Rated short-circuit duration |
S |
four |
| Rated breaking current of a single capacitor bank |
A |
six hundred and thirty |
| Rated back-to-back capacitor bank breaking current |
A |
four hundred |
| Rated operating sequence |
|
Fen-0.3S-180S-Fen |
| Rated short-circuit breaking current breaking times |
time |
twenty |
| mechanical life |
time |
ten thousand |
| Contact self closing force |
N |
170±30 |
| Contact reaction force |
N |
320±30 |
| Circuit resistance at lower limit of rated contact pressure |
uΩ |
≤30 |
| Thickness of allowable wear of contacts |
mm |
three |
| Gas pressure inside the vacuum arc extinguishing chamber |
Pa |
≤1×10 |
| Quality of the sports section |
kg |
four point one |
| Quality of vacuum arc extinguishing chamber |
kg |
twelve point eight |
Mechanism characteristics and parameters of vacuum switch equipment for TD-40.5/1600-31.5 vacuum arc extinguishing chamber
| parameter item |
unit |
parameter |
| contact gap |
mm |
25±2 |
| Average opening speed |
m/s |
2.0±0.3 |
| Average closing speed |
m/s |
0.8±0.2 |
| Rated contact pressure |
N |
3100±200 |
| Contact closing bounce time |
ms |
≤3 |
| Non synchronous closing and opening of contacts |
ms |
≤2 |
| Rebound amplitude of the opening contact |
mm |
≤2 |