| Product name: | JZ14 series AC/DC intermediate relay | ||||||
| specification: | ![]() |
||||||
| Category: | low-voltage electrical apparatus -- intermediate relay | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
JZ14 series AC/DC intermediate relay, hereinafter referred to as relay, is suitable for AC 50Hz voltage circulation of 380V and below; Used to increase the signal size and quantity in control circuits with a DC voltage of 220 volts or less.
4.1 The rated current of the relay contacts is 5A. The rated control capacity levels are JF2 and ZF2.
4.2 The working system of the relay is:
1. Intermittent long-term work system
2 Repetitive Short term Work System
The rated operating frequency of the repetitive short-term working system is 2000 times per hour, with a power on duration of 40.
Note: When a relay is used for long-term operation, its coil temperature rise is allowed to be assessed based on intermittent or repeated short-term operation.
The mechanical lifespan of the relay should not be less than 10 million cycles.
The electrical life of relay contacts under rated operating frequency and in accordance with the table and working conditions should not be less than 1 million times.
The hot state pull in voltage of the relay shall not exceed 85 rated operating voltage; The cold release voltage should be greater than 5 rated operating voltages.
The inherent action time of the 4.6 relay's suction and release shall not exceed 0.05 seconds.