HomeYour location:Homelow-voltage electrical apparatusrelayImpact relay → JC-23/23A type impulse relay
Column tabs 
Product name: JC-23/23A type impulse relay
specification: 暂无图片
  Zoom No image available
Category: low-voltage electrical apparatus -- Impact relay
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


JC-23/23A type impulse relayDetailed product description:Column tabs

Purpose:
Impact relays are mainly used in relay protection and safety automatic device circuits for various types of fault centralized alarm starting sound, that is, components that repeat actions in the central sound alarm circuit of power stations, substations, and related engineering systems.

Relay model name:

Model Description of JC-23/23A Impact Relay

Working Principle:
The impact relay consists of a transformer, measurement sampling pulse width detection, trigger memory, automatic reset, delayed action and delayed return, and voltage stabilization circuit. When a certain circuit light path sign lights up, current flows through the primary winding of the inverter in the relay, inducing a pulse voltage on the secondary winding of the inverter. This voltage is sent to the action measurement and return measurement circuits respectively. Since the action measurement only has output when the light is on and no output when the light is off, the return measurement does not have output at the same time. Therefore, the action measurement and return measurement will not have output at the same time. Then measure the input pulse width detector to avoid relay misoperation caused by induced voltage in the circuit. The pulse width measurement output is sent to the action delay and return delay circuits, and when it meets the set time, it is output to the outlet relay.
Due to the memory function of the triggering circuit, the pulse is no longer detected after the relay is activated until the light signal is turned off or the external reset causes the relay to return, and then the relay enters the loop state again.
The relay has memory functions for both action and return, with the aim of ensuring interoperability between accident and warning signals in starting the audio system. Additionally, the relay is equipped with an external reset interface.


Schematic diagram of JC-23/23A impact relay

Usage:
Typical Connection Diagram

JC-23/23A type impulse relay wiring diagram

Main technical parameters:
4.1 Rated DC auxiliary voltage: 48V, 110V, 220V.
4.2 Minimum impulse action and reset current: JC-23 is 0.1A; JC-23A is 0.01A.
4.3 Maximum thermal stability current: JC-23 is 4A; JC-23A is 0.8A.
4.4 Rated number of impact circuits: JC-23 shall not be less than 40; JC-23A shall not be less than 80.
4.5 Action and return delay setting range: 0-9s, error ± 10%.
4.6 Power consumption
4.6.1 The power consumption shall not exceed 6W at the rated DC voltage.
4.6.2 Under maximum thermal stability current, the power consumption of the measurement circuit shall not exceed 2W.
4.7 Contact Performance
4.7.1 Contact Capacity: In a DC circuit with a voltage not exceeding 250V, a current not exceeding 5A, and a time constant of 40ms, the contact breaking capacity is 50W. In an AC circuit, it is 500VA (coso=0.4 ± 0.1), and the contact long-term current is 5A.
4.7.2 Relay contact forms JC-23 and 23A provide one set of conversion contacts and one set of normally open contacts.
4.8 Working conditions
a) The usage location does not allow explosive media, and the surrounding media should not contain corrosive metals, gases that damage insulation, or conductive media. It is not allowed to be filled with water vapor or have serious mold presence;
b) Strong vibrations and impacts are not allowed in the usage location;
c) The usage location should have facilities to defend against rain, snow, wind, and sand;
d) The usage location does not allow an external magnetic induction intensity exceeding 1.5mT.
The conductive circuits of the 4.9 dielectric strength relay should be able to withstand an AC test voltage of 2kV (effective value), 50Hz between exposed non charged metal parts and casings, between input circuits and contacts, and between different circuits. After a 1-minute test, there should be no insulation breakdown or flashover phenomenon.
4.10 Electrical anti-interference relays shall comply with GB7261 and GB6261 "Electrical anti-interference test for emergency protection devices of static relays".

Wiring diagram behind the relay:

Contact diagram of JC-23/23A impact relay


Relay external dimensions and opening dimensions:
Refer to Figure 4 in the general structure.

Ordering instructions:
8.1 Product model, name, auxiliary voltage level, etc.
8.2 Order Quantity.
8.3 Supply completeness: 1 copy of product manual.

JC-23/23A type impulse relay(No image available)
Product Category