| Product name: | DL-10 series current relay | ||||||
| specification: | ![]() |
||||||
| Category: | low-voltage electrical apparatus -- current relay | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
1 Purpose
The DL-10 series current relay is used as a starting element for overload and short circuit protection in motors, transformers, and transmission lines.
Overview of Structure 2
2.1 The relay system is electromagnetic instantaneous action, with two coils in the magnetic system. The coil leads are connected to the terminals of the relay base, and a connecting piece (factory accessory) can be used to change the series connection of the coils to parallel connection, thereby doubling the setting range of the relay. The internal wiring diagram of the relay is shown in Figure 1.
The relay is installed on a vertical panel and can be wired in front of or behind the board.

According to this, DL-11 DL-12 DL-13
Figure 1 Internal wiring diagram of DL-10 series relay (back view)
3 Technical data
3.1 Disconnecting capacity of contacts: When the voltage is not greater than 220V and the current is not greater than 2A, it is 50W in DC circuits with inductive loads (time constant T is not greater than 5 × 10-3s); in AC circuits (COS Φ=0.4), it is 250VA.
3.2 Action time: When the setting value is 1.1 times, the action time shall not exceed 0.12s; when the setting value is 2 times, the action time shall not exceed 0.04s.
3.3 Dielectric Strength: Each circuit of the relay should withstand a test of AC 50Hz, voltage 2kV, and duration of 1 minute between non charged metal parts.
The weight of the relay is approximately 1 kg.
The other main technical data of the 3.5 current relay are shown in Table 1.
3.6 The appearance and installation hole size of the relay are shown in Figure 2 and Figure 3 respectively. ·
4 Ordering Instructions
Please indicate when placing an order
4.1 Model and name of relay.
4.2 Maximum current setting value.
4.3 Wiring method: (pre board wiring or post board wiring). If not specified, provide accessories for wiring behind the board.
|
model |
maximum set value (A) |
tuning scope (A) |
Coil series connection |
Parallel connection of coils |
At the minimum setting Power at current Consumption (VA) |
Contact type |
return coefficient | |||||
|
Action current (A) |
Thermal stability current A |
Action current (A) |
Thermal stability current A |
Dynamic combination |
move sever | |||||||
|
long-term |
Is |
long-term |
Is | |||||||||
|
DL—11 DL—12 Dl—13 |
zero point zero one |
zero point zero zero two five - zero point zero one |
zero point zero zero two five - zero point zero zero five |
zero point zero two |
zero point six |
zero point zero zero five - zero point zero one |
zero point zero four |
one point two |
zero point zero eight |
one one |
one one |
zero point eight |
|
DL—11 DL—12 DL—13 |
zero point zero four |
zero point zero one - zero point zero four |
zero point zero one - zero point zero two |
zero point zero five |
one point five |
zero point zero two - zero point zero four |
zero point one |
three |
zero point zero eight |
one one |
one l | |
|
DL—11 DL—12 DL—13 |
zero point zero five |
zero point zero one two five - zero point zero five |
zero point zero one two five - zero point zero two five |
zero point zero eight |
two point five |
zero point zero two five - zero point zero five |
zero point one six |
five |
zero point zero eight |
one one |
one one | |
|
Dl—11 DL—12 DL—13 |
zero point two |
zero point zero five - zero point two |
zero point zero five - zero point one |
zero point three |
twelve |
0.1—0.2 |
zero point six |
twenty-four |
zero point one |
one one |
one one | |
|
DL—11 DL—12 DL—13 |
zero point six |
zero point one five - zero point six |
zero point one five - zero point three |
one |
forty-five |
0.3—0.6 |
two |
ninety |
zero point one |
one one |
one one | |
|
DL—11 DL—12 DI—13 |
two |
0.5—2 |
0.5—1 |
four |
one hundred |
1-2 |
eight |
two hundred |
zero point one |
one one |
one one | |
|
DL—11 DL—12 DL—13 |
six |
1.5—6 |
1.5-3 |
ten |
three hundred |
3-6 |
twenty |
six hundred |
zero point one |
one one |
one one | |
|
DL—11 DL—12 DL—13 |
ten |
2.5—10 |
2.5—5 |
ten |
three hundred |
5—10 |
twenty |
six hundred |
zero point one five |
one one |
one one | |
|
DL—11 DL—12 DL—13 |
twenty |
5—20 |
5—10 |
fifteen |
three hundred |
10—20 |
thirty |
six hundred |
zero point two five |
one one |
l one | |
|
DL—11 DL—12 DL—13 |
fifty |
12.5—50 |
12.5—25 |
twenty |
four hundred and fifty |
25-50 |
forty |
nine hundred |
one |
one one |
one one | |
|
DL—11 DL—12 DL—13 |
one hundred |
25—100 |
25—50 |
twenty |
four hundred and fifty |
50—100 |
forty |
nine hundred |
two point five |
one one |
one one | |
|
DL—11 DL—12 DL—13 |
two hundred |
50—200 |
50-100 |
twenty |
four hundred and fifty |
100—200 |
forty |
ninety |
ten |
one one |
one one |
zero point seven |

Figure 2: The external dimensions of the DL-10 series relay are front board wiring and rear board wiring