DZS-100Q series intermediate relayDetailed product description:Column tabs
Application of DZS-100Q series intermediate relay
The DZS-100Q series intermediate relay is used as an auxiliary relay in DC operated protection circuits to increase the number or capacity of contacts of the main protection relay. DZS-115Q and DZS-117Q are delay action relays, DZS-127Q and DZS-136Q are delay voltage action and current protection relays, and DZS-145Q is a delay return relay.

2 Structure and principle
2.1 The DZS-100Q series intermediate relay adopts embedded installation, and the main body is a plug-in structure.
The main body of the DZS-100Q series intermediate relay is the same as that of the DZS-100 series intermediate relay.
2.3 The DZS-100Q series relay is a pull in electromagnetic relay, with the coil of the relay mounted on a cylindrical iron core of a mountain shaped magnetic conductor. The DZS-115Q and 117Q models have only one working winding (voltage winding), while the DZS-127Q and 136Q models have one working winding (voltage winding) and two holding windings (current winding). Damping rings are simultaneously installed on the cylindrical iron core above or below the coil, thereby obtaining delayed action or delayed return of the relay.
The dynamic and static contact systems of the 2.4 relay are respectively fixed on the armature and yoke of the magnetic conductor. The armature and yoke are hinged with support pillars, and the relay is returned and in the open position by the action of a tension spring.
The internal wiring of the 2.5 relay is shown in Figure 1.

DZS-100Q series intermediate relay contact diagram

Figure 1 Internal wiring diagram of DZS-100Q series intermediate relay


3 DZS-100Q series intermediate relay technical data
3.1 Relays are classified according to their rated data and contact form and listed in Table 1.

model

Rated data

Number of contact points (paid)

Voltage (V)

Current (A)

Dynamic combination

Dynamic interruption

DZS—115Q

DZS—145Q

220,110,48,24

two

two

DZS—117Q

220,110,48,24

four

DZS—127Q

220,100

1,2,4

four

48,24

2,4,6

DZS—]36Q

220,110

1,2,4

three

48,24

2,4,6


3.2 Operating voltage: not exceeding 70% of the rated voltage.
3.3 Operating current: not less than 0.06s (excluding DZS-145Q type).
3.4 Holding current: not exceeding 80% of the rated current (only applicable to DZS-127Q and 136Q models).
3.5 Return time
3.5.1 DZS-145Q type, at rated voltage, the power on time shall not be less than 0.5s, and then the power supply shall be cut off. The return time of the relay shall not be less than 0.8s.
3.5.2 Other types of relays should return immediately after cutting off the power supply.
3.6 Winding temperature rise: When the ambient temperature is+40 ℃.
3.6.1 The voltage winding can withstand 110% of the rated voltage for a long time, not exceeding 65k.
3.6.2 The current winding is allowed to pass 3 times the rated current for 5 seconds.
3.7 Power consumption: at rated value.
3.7.1 DZS-115Q and 117Q models, not exceeding 3.5w.
3.7.2 DZS-127Q and 136Q types, with voltage winding not exceeding 5.5W and current winding not exceeding 2.5W.
3.7.3 DZS-145Q type, not exceeding 6.5W.
3.8 Contact Capacity: Complies with the specifications in Table 2.

Load

Voltage (V)

Maximum breaking current (A)

Long term connected current (A)

direct current

communication

No sensation

two hundred and twenty

one

five

one hundred and ten

five

five

Feeling (T ≤ 5 × 10-3S)

two hundred and twenty

zero point four

five

one hundred and ten

four

five

*

two hundred and twenty

five

five

one hundred and ten

ten

five


*This item is for reference only

3.9 Dielectric Strength: All circuits of the relay shall withstand AC 50Hz, voltage 2kV, and a 1-minute test between the casing and non electrified metal parts, as well as between circuits that are not electrically connected.
The weight of the 3.10 relay shall not exceed 1.6kg.
The appearance and installation dimensions of the 3.11 relay are shown in Figure 2.
DZS-100Q series intermediate relay external dimensions

Figure 2 Appearance and installation dimensions of DZS-100Q series intermediate relay

4 Ordering Instructions
4.1 When placing an order, please specify
The name and model of the relay.
Rated voltage or rated current.
Number of relays.
4.2 The coil resistance is the same as the DZS-100 series.