HomeYour location:Homelow-voltage electrical apparatusrelayOther relays → JN-20 Series Reverse Current Relay
Column tabs 
Product name: JN-20 Series Reverse Current Relay
specification: 暂无图片
  Zoom No image available
Category: low-voltage electrical apparatus -- Other relays
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


JN-20 Series Reverse Current RelayDetailed product description:Column tabs
purpose
The JN-20 series reverse current relay is used to prevent reverse current from being generated by DC power sources, such as DC motors. When used in parallel in public networks or charging batteries, the relay will activate when the direction of the power current changes.

Overview of Structure 2
The relay system is made using the principle of polarization, and it has a voltage coil and a current coil. When the current is greater than 800A, there is no current coil, and the relay is directly installed on the busbar.
Relays are divided into ten types according to their rated voltage, and the voltage coils are designed according to their rated voltage.
Relays are classified into twelve types based on their rated current, and there are three types of relay structures depending on the magnitude of the rated current.
The relay has a movable contact or a movable contact.
During installation, the shaft of the relay must be in a horizontal position with the contacts located directly above.

Technical data of JN-20 series reverse current relay
3.1 The specifications for relays are shown in Table 1

model

JN21

JN22

JN23

contact form

1. Dynamic combination

1. Dynamic interruption

1. Dynamic combination

1. Dynamic interruption

1. Dynamic combination

1. Dynamic interruption

Current specifications

(A)

6,12,25,50,100,

150,200,300

400,600,800

one thousand and six hundred

The current specifications should be

(A)

6,12,24,30,36,

48,50,60,110,220

6,12,24,30,36,

48,50,60,110,220

6,12,24,30,36,

48,50,60,110,220


The diameter of the wiring screw varies depending on the rated current (6 to 800A), as shown in Table 2

Current (A)

6,12,25,50

100,150,200,300

400,600,800

Diameter (mm)

M6

M10

M12


3.2 Action value: The relay should be able to operate when the reverse current value introduced into the relay current coil is not greater than 15% of the rated current value.
3.3 Return value: When the reverse current value entering the relay current coil is 50% of the rated current value, disconnecting the current circuit can reliably return.
In the current coil of the relay, after passing a forward surge current of 200% of the rated value for 1 second, the relay should not experience misoperation or mechanism damage.
The power consumption of the 3.5 voltage winding shall not exceed 3.5W.
When the voltage is not greater than 220V and the current is not greater than 5A, the contact breaking capacity in a DC inductive load (time constant of 5H10-3S) circuit is 100W.
When the temperature of the surrounding medium is+40 ℃, the voltage coil of the relay should be able to withstand 110% of the rated voltage for a long time, and its temperature rise should not exceed 60K.
3.8 All conductive parts of the relay should withstand AC 50Hz, 1KV voltage for 1 minute without breakdown or flashover due to the dielectric strength of the casing.
The weight of the 3.9 relay is 2Kg
The appearance and installation dimensions of the 3.10 relay are shown in Figure 1, Figure 2, and Figure 3.

JN-20 series reverse flow relay installation size 1

Figure 1 JN-21

3.10.1 JN-21 type reverse current relay is fastened to the screen board with M8 diameter screws, and its external dimensions are shown in Figure 1.
3.10.2 JN-22 type reverse current relay is connected to the cut-off of the busbar, and the outlet of the current coil is equipped with installation parts. Its external dimensions are shown in Figure 2.

JN-20 series reverse flow relay installation size 2
Figure 2 JN-22

3.10.3 JN-23 type reverse current relay does not have a current coil and is directly installed on the busbar. Its external dimensions are shown in Figure 3. When the width of the busbar is greater than 40mm, it should be cut according to Figure 4.

JN-20 series reverse flow relay installation size 3

Figure 3 JN-23

JN-20 series reverse current relay opening size

Figure 4: Busbar

4 Ordering Instructions
4.1 Name and model of relay.
4.2 Rated current.
4.3 Rated voltage.
4.4 Contact Form.

JN-20 Series Reverse Current Relay(No image available)
Product Category
All product information on this website is translated by Baidu machine translation, which may not be completely accurate and is only for reference