HomeYour location:Homelow-voltage electrical apparatusLow voltage protectorsurge protector → M-SP series surge protection device
Column tabs 
Product name: M-SP series surge protection device
specification: M-SP series surge protection device
  Zoom Zoom in on the image
Category: low-voltage electrical apparatus -- surge protector
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


M-SP series surge protection deviceDetailed product description:Column tabs
Description of M-SP series surge protection device

This series of products is suitable for lightning and surge protection in the PZOB lightning protection zone and the LPZ1 to LPZ2 (Class C or II) power lines.
The core component of this product adopts the latest high-capacity surge absorber MOV, which has been rigorously screened and has stable quality.
The product has the advantages of high current capacity, low output residual voltage, and fast response to overvoltage (action time less than 25ns), which can effectively protect electrical equipment.
Install a failure release device that can automatically disconnect the protector from the power grid when it fails due to overheating or breakdown.
This series of products has complete functions, modular packaging, and standard 35mm wide electrical installation rails for easy installation and replacement.
The shell is made of reinforced flame-retardant PBT material, which meets electrical safety standards.
Can attach alarm remote signaling

Product installation location and application
The C-level module series is usually installed at the junction of LPZOB or LPZ1 area or LPZ2 area, that is, Class II, and is usually installed in distribution cabinets and boxes.
Combining single poles into various configurations, suitable for TN-S, TN-C, TN-C-S, TT, IT and other power supply systems.
Widely used for second level lightning protection in power supplies. Usually installed at the distribution cabinet; Floor distribution boxes, computer centers, telecommunications rooms, security monitoring centers, cable TV rooms, building control rooms, elevator control rooms, fire control centers, industrial control hospital operating rooms, monitoring rooms, and distribution boxes containing electronic medical equipment; It can also be installed in the main distribution box of residential buildings below six floors and in the distribution box of dispersed villas.
Before the surge protector, a commercially available 63A fuse must be installed as a backup safety device for the protector.
The protector is suitable for indoor installation, and waterproof measures should be added outdoors.
All wiring must ensure firm and reliable electrical connection, and lightning protection grounding should comply with lightning protection specifications (recommended grounding resistance not exceeding 10 Ω), and the grounding wire should be short and straight (≤ 0.5 meters). The wire diameter specifications are shown in the wire specification table.

Installation location and application of M-SP series surge protection device

model
M-SP-B
Maximum continuous operating voltage Uc
280V,335V,385V,460V ……50Hz/60Hz
Limit voltage Up (8/20 μ S, In)
≤2.2KV
≤2.5KV
Nominal discharge current In (8/20 μ S,)
30KA
40KA
Maximum discharge current Imax (8/20 μ S)
60KA
80KA
response time
≤25ns
Maximum backup fuse strength
63A backup protection device
Installation of wiring method
parallel connection
bracket installation
35mm wide electrical installation guide rail
Conductor cross-section
Multi strand wire (L \ N) ≥ 10mm2 Multi strand wire (PE) ≥ 16mm2
Normal or faulty
possess
Indicate the material of the casing
Enhanced flame retardant PBT
Overall dimensions
90 x 27 x 62mm
Installation width
1 standard module
reference standard
IEC61643,GB18802-2002,GB50343-2004
Installation location
Installed in the distribution box, Class B/II


Schematic diagram and external dimensions of M-SP series surge protection device

Technical Specifications

model
M-SP-D M-SP-C
Maximum continuous operating voltage Uc
280V,335V,385V,460V……50Hz/60Hz
Limit voltage Up (8/20 μ S, In)
≤1.2KV
≤1.5KV
≤1.8KV
Nominal discharge current In (8/20 μ S,)
5KA
10KA
20KA
Maximum discharge current Imax (8/20 μ S)
10KA
20KA
40KA
response time
≤25ns
Maximum backup fuse strength
63A backup protection device
Installation of wiring method
parallel connection
bracket installation
35mm wide electrical installation guide rail
protection level
Ip20
Conductor cross-section
Multi strand wire (L \ N) ≥ 10mm2 Multi strand wire (PE) ≥ 16mm2
Normal or faulty
possess
Indicate the material of the casing
Enhanced flame retardant PBT
Overall dimensions
90 x 18 x 62mm
Installation width
1 standard module
reference standard
IEC61643,GB18802-2002,GB50343-2004
Installation location
Installed in the distribution box, C/D level/II level


Main electrical schematic diagram
M-SP series surge protection device wiring diagram

M-SP series surge protection device
Product Category