Product name: GPN-32L( Phase line+neutral line+leakage protection circuit breaker
specification: GPN-32L( Phase line+neutral line+leakage protection circuit breaker
  Zoom Zoom in on the image
Category: low-voltage electrical apparatus -- Residual Current Circuit Breaker
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


GPN-32L( Phase line+neutral line+leakage protection circuit breakerDetailed product description:Column tabs
GPN-32L (phase line+neutral line+leakage) protection circuit breaker provides high-level ground leakage current protection, reliable overvoltage protection, as well as overload and short circuit protection:
Provide protection for indirect contact
Provide supplementary protection for direct contact
Provide protection against insulation faults in electrical equipment
Provide protection against overvoltage faults.

Technical parameters of GPN-32L (phase line+neutral line+leakage) protection circuit breaker

Phase line+neutral line protection
Rated current (30 ℃): 6A-32A
Rated voltage: 50V-230V AC
Breaking capacity: 4500A (IEC61009 and GB16917)
The overvoltage trip limit is 280V ± 5%
Ground leakage action current: 30mA, AC class
Electronic leakage protection filtering device can prevent false tripping caused by instantaneous voltage (interference from lighting and other equipment lines) and instantaneous current (such as high-capacity load lines).
Release characteristics:
C-type (5-10) In instantaneous release;
Wiring: wires of 10mm2 and below;
Width: 36mm (4 times modulus);
The leakage trip indicator is located on the front of the device;
The product complies with the IEC61009/GB16917 standard
Application Guide
Press the test button once a month to check the operation of the leakage protection device;
When the leakage protection device is activated, there is a red mechanical indicator on the front of the device;
When the circuit breaker is closed again, the leakage protection device automatically resets
GPN-32L( Phase line+neutral line+leakage protection circuit breaker