HomeYour location:Homespare parts and accessoriesvacuum interrupterCeramic arc extinguishing chamber → TD-7.2/400-10 Vacuum arc extinguishing chamber for circuit breakers (mining)
Column tabs 
Product name: TD-7.2/400-10 Vacuum arc extinguishing chamber for circuit breakers (mining)
specification: TD-7.2/400-10 Vacuum arc extinguishing chamber for circuit breakers (mining)
  Zoom Zoom in on the image
Category: spare parts and accessories -- Ceramic arc extinguishing chamber
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


TD-7.2/400-10 Vacuum arc extinguishing chamber for circuit breakers (mining)Detailed product description:Column tabs
Main technical parameters of vacuum arc extinguishing chamber for TD-7.2-400-10 circuit breaker (mining)

serial number

parameter name

unit

numerical value

one

rated voltage

KV

seven point two

two

rated current

A

four hundred

three

rated frequency

HZ

fifty

four

Short term (1-minute) power frequency withstand voltage

KV

thirty-two

five

Lightning impulse withstand voltage (peak value)

KV

sixty

six

Rated short-circuit breaking current

KA

ten

seven

Rated short-time withstand current

KA

ten

eight

Rated short-circuit duration

S

four

nine

Rated peak withstand current

KA

twenty-five

ten

Rated short-circuit closing current

KA

twenty-five

eleven

Rated breaking current of a single capacitor bank

A

six hundred and thirty

twelve

Rated back-to-back capacitor bank breaking current

A

four hundred

thirteen

Rated short-circuit breaking current breaking times

time

thirty

fourteen

mechanical life

time

ten thousand

fifteen

Contact self closing force

N

85±20

sixteen

Contact reaction force

N

100±40

seventeen

Circuit resistance at lower limit of rated contact pressure

μ Ω

≤30

eighteen

Allowable wear thickness of contacts

mm

three

nineteen

Internal gas pressure

Pa

≤1.33×10-3

twenty

Quality of moving parts

kg

zero point six



Mechanical characteristics and parameters of vacuum switch equipment for product matching

one

contact gap

mm

8±1.0

two

Average opening speed

m/s

1.0±0.2

three

Average closing speed

m/s

0.8±0.2

four

Rated contact pressure

N

650±50

five

Contact closing bounce time

ms

≤2

six

Rebound amplitude of the opening contact

ms

≤1.5

seven

Contact stroke of contacts

mm

two+0.50

Dimensions of vacuum arc extinguishing chamber for TD-7.2-400-10 circuit breaker (mining)
TD-7.2-400-10 vacuum arc extinguishing chamber for circuit breakers (mining)

TD-7.2/400-10 Vacuum arc extinguishing chamber for circuit breakers (mining)
Product Category
All product information on this website is translated by Baidu machine translation, which may not be completely accurate and is only for reference