| Product name: | SR93/94 Series 0.3 Grade PID Regulator | ||||||
| specification: | ![]() |
||||||
| Category: | low-voltage electrical apparatus -- industrial control equipment | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
Number |
The SR90 series is a 0.3 level PID intelligent regulator with dual four position display, dual output, analog transmission output, digital communication, disconnection alarm, upper and lower limit alarm and other functions. The front panel protection level is IP66. | |||||||
|
SR93- |
DIN standard: height 96 x width 96 x depth 110mm, panel opening size 92 x 92mm | |||||||
|
SR94- |
DIN standard: height 96 x width 48 x depth 110mm, panel opening size 92 x 45mm | |||||||
|
Input type and measurement range Display range of DC input type -1999-9999 decimal point position can be set |
eight free input |
Thermocouple: B:0~1800,R:0~1700,S:0~1700,K1:100.0~400.0,K2:0.0~800.0,K3:-200~1200,E:0~700,J:0~600,T:-199.9~200.0,N:0~1300,PLII:0~1300,Wre5-26:0~2300,U:-199.9~200.0,L:0~600 ℃ Pt100 platinum resistance: -200~600, -100.0~100.0, -50.0~50.0, 0.0~200.0 ℃ (JPt100 omitted) DC millivolts: -10~10, 0~10, 0~20, 0~50, 10~50, 0~100mV | ||||||
|
four |
DC current: 0-20mA, 4-20mA, input impedance: 250 Ω | |||||||
|
six |
DC voltage: -1~1, 0~1, 0~2, 0~5, 1~5, 0~10V DC load impedance:<600K Ω | |||||||
|
Adjust output (1) type |
Y- |
Relay contact, time proportional period: 1-120 seconds, contact capacity: 240V AC 2A/resistive | ||||||
|
I- |
Current 4-20mA DC, load impedance<600 Ω | |||||||
|
P- |
Solid state relay drive, 12 ± 1.5V DC/maximum 30mA, time proportional period 1-120 seconds | |||||||
|
V- |
Voltage 0-10V DC, load current<2mA | |||||||
|
Adjust output (2) type Positive and negative effects can be set (Optional) |
N- |
nothing | ||||||
|
Y- |
Relay contact, time proportional cycle 1-120 seconds, contact capacity: 240V AC 2A/resistive | |||||||
|
I- |
Current 4-20mA DC, load impedance<600 Ω | |||||||
|
P- |
Solid state relay drive, 12V ± 1.5V DC/maximum 30mA, proportional period 1-120 seconds | |||||||
|
V- |
Voltage 0-10V DC, load current<2mA | |||||||
|
power supply |
90- |
100~240V AC±10% ,50/60Hz | ||||||
|
08- |
24V AC/DC±10%, 50/60Hz | |||||||
|
Event output (optional) (Heater disconnection alarm is only available when adjusting the output (1) to Y-shaped/P-type output) |
0 |
nothing | ||||||
|
one |
Event output: EV1, EV2 contact capacity: 240V AC 1A/resistive | |||||||
|
two |
Event output: EV1 and 30A heater disconnection alarm (contact capacity: 240V AC 1.5A/resistive) | |||||||
|
three |
Event output: EV1 and 50A heater disconnection alarm (contact capacity: 240V AC 1.5A/resistive) | |||||||
|
option (Select only one option) |
00 |
nothing | ||||||
|
Simulate sending |
thirty |
0~10mV DC, Output impedance: 10 Ω | ||||||
|
forty |
4~20mA DC, Load impedance<300 Ω | |||||||
|
sixty |
0~10V DC, Load current<2 mA | |||||||
|
Dual Setpoint (SB) |
08 |
1 point (range: -1999~5000), no voltage contact or OC gate input | ||||||
|
Simulate sending and dual set values (SB) |
thirty-eight |
0~10mV DC, Output impedance: 10 Ω+SB (1 point) | ||||||
|
forty-eight |
4~20mA DC, Load impedance<300 Ω+SB (1 point) | |||||||
|
sixty-eight |
0~10V DC, Load current<2 mA+SB (1 point) | |||||||
|
Digital communication interface |
05 |
RS485 address: 1-255 | ||||||
|
07 |
RS232C | |||||||
SR93/94 series 0.3-level PID regulator