The LW36-126 outdoor self powered high-voltage sulfur hexafluoride circuit breaker is suitable for use in AC 50Hz, 110kV power systems. It can be used as a control and protection equipment for power systems, as well as as as a contact circuit breaker. This product was awarded the 2001 National Economic and Trade Commission Key New Product Recommendation Certificate.
Main technical characteristics of LW36-126 outdoor high-voltage sulfur hexafluoride circuit breaker
1. The circuit breaker adopts the principle of self extinguishing arc, with strong breaking capacity, and can break up to 20 times at full capacity;
2. Equipped with a new type of highly reliable spring operated mechanism, the mechanical reliability can reach 60000 times;
3. Equipped with CT24 or new spring mechanism, high mechanical reliability and low maintenance workload;
4. High insulation level, able to meet both national and IEC standards simultaneously;
5. Thick steel plate integral frame with high seismic resistance.
Main technical parameters of LW36-126 outdoor high-voltage sulfur hexafluoride circuit breaker:
| serial number |
project |
unit |
Technical Parameters |
| one |
altitude |
m |
1000(3000) |
| two |
ambient temperature |
℃ |
-25~+40 |
| three |
rated voltage |
kV |
one hundred and twenty-six |
| four |
rated current |
A |
2500 3150 |
| five |
rated frequency |
Hz |
fifty |
| six |
Rated short-circuit breaking current |
kA |
31.5 40 |
| seven |
Rated short-circuit closing current |
kA |
80 100 |
| eight |
Rated short-time withstand current |
kA |
31.5 40 |
| nine |
Rated peak withstand current |
kA |
80 100 |
| ten |
Rated short-time power frequency withstand voltage |
kV |
Ground: 230 Between fracture surfaces: 230+73* |
| eleven |
Rated lightning impulse withstand voltage |
kV |
Ground: 550 Between fracture: 550+103* |
| twelve |
Rated short-circuit current duration |
s |
four |
| thirteen |
Rated out of step breaking current |
A |
8 10 |
| fourteen |
Near area fault breaking current |
|
90% 75% |
| fifteen |
Rated line charging switching current |
A |
thirty-one point five |
| sixteen |
Rated operating sequence |
|
O-0.3s-CO-180s-CO |
| seventeen |
SFsixGas pressure (20 ℃ gauge pressure) |
MPa |
zero point six |
| eighteen |
mechanical life |
time |
six thousand |
| nineteen |
Control circuit voltage |
V |
DC110 or 220 |
LW36-126 Outdoor High Voltage Sulfur Hexafluoride Circuit Breaker